Chapter 4: Using the Command Line Interface
156
Variables:
•
<outlets1> is one or multiple outlet numbers to be set as critical outlets. Use commas to separate outlet numbers.
Use a dash for a range of consecutive outlets. For example,
3-8
represents outlets 3 to 8.
•
<outlets2> is one or multiple outlet numbers to be set as NON-critical outlets. Use commas to separate outlet numbers.
Use a dash for a range of consecutive outlets. For example,
3-8
represents outlets 3 to 8.
Enabling or Disabling Data Logging
This command enables or disables the data logging feature.
config:#
pdu dataRetrieval <option>
Variables:
•
<option> is one of the options:
enable
or
disable
.
Option
Description
enable
Enables the data logging feature.
disable
Disables the data logging feature.
For more information, refer to
Setting Data Logging
in the PDU With RackLink User Manual at
www.middleatlantic.com/resources/power-downloads.aspx
Setting Data Logging Measurements Per Entry
This command defines the number of measurements accumulated per log entry.
config:#
pdu measurementsPerLogEntry <number>
Variables:
•
<number> is an integer between 1 and 600. The default is 60 samples per log entry.
For more information, refer to
Setting Data Logging
in the PDU With RackLink User Manual at
www.middleatlantic.com/resources/power-downloads.aspx
Setting the Z Coordinate Format for Environmental Sensors
This command enables or disables the use of rack units for specifying the height (Z coordinate) of environmental sensors.
config:#
pdu externalSensorsZCoordinateFormat <option>