• Allows fans to operate at speeds proportional to temperature inside of enclosure
• Available as a stand-alone or MPR raceway mounted module
(See A&E spec sheet # 96-959)
• Can be turned on and off via a local switch
• Status LED’s indicate fan speed setting
• Allows control of up to 4 qty. 120 volt fans
• Finished in a durable min-spangle galvanized steel
• UL Listed in the US and Canada
FC Series proportional speed fan control keeps equipment cool
while reducing maintenance requirements and extending fan life
FC-4 - Mounts In MPR Raceway
Thermostatic Fan Control module shall be Middle Atlantic Products model # FC-4.
Module shall mount in Modular Power Raceway on an unswitched circuit. Power
input shall be 120VAC - 60HZ. Power output shall consist of 4 NEMA 1-15R (2
prong) outlets, 30 to 120 VAC at 1 amp, to control up to 4 fans. FC-4 switch settings
shall be Off (fan control module is off), On (Fan is on full-speed) or Auto
(thermostatic fan controls fan speed, proportional to temperature) and shall be
indicated by status LED’s. Module shall be protected by user serviceable 4 amp fuse.
Three-position pluggable jumper shall be provided to shift positions of
temperature control range. Fan control module shall have a user definable
temperature range (80
O
F to 90
O
F, 85
O
F to 95
O
F, 90
O
F to 100
O
F). Module shall be
factory-set to 85
O
F to 95
O
F range. Probe with 5 ft. wire shall be provided for
temperature sensing. FC-4 shall be manufactured for indoor use in dry locations
only.
FC-4-1C - Stand-Alone
Thermostatic Fan Control module shall be Middle Atlantic Products model # FC-4-1C.
Module shall be stand-alone and shall mount with integral mounting flanges. Power
input shall be 120VAC - 60HZ. Power output shall consist of 4 NEMA 1-15R
(2 prong) outlets, 30 to 120 VAC at 1 amp, to control up to 4 fans. FC-4-1C switch
settings shall be Off (fan control module is off), On (Fan is on full-speed) or Auto
(thermostatic fan controls fan speed, proportional to temperature) and shall be
indicated by status LED’s. Module shall be protected by user serviceable 4 amp fuse.
Three-position pluggable jumper shall be provided to shift positions of
temperature control range. Fan control module shall have a user definable
temperature range (80
O
F to 90
O
F, 85
O
F to 95
O
F, 90
O
F to 100
O
F). Module shall be
factory-set to 85
O
F to 95
O
F range. Probe with 5 ft. wire shall be provided for
temperature sensing. FC-4-1C shall be manufactured for indoor use in dry locations
only.
96-980 / rev 1a / 4-11-03
Features
Architects’ and Engineers’ Specifications
96-980 / rev 1a / 4-11-03 / FC
Series Thermostatic Fan Control
FC-4
FC Series Thermostatic Fan Control
w w w . m i d d l e a t l a n t i c . c o m
Middle Atlantic Products, Inc.
Engineered Mounting Solutions for Low Voltage Applications
US: Riverdale, NJ • Simi Valley, CA • Harvey, IL • Voice: 973-839-1011 Fax: 973-839-1976 • www.middleatlantic.com
Canada: Ottawa, ON • Burnaby, BC • Voice: 613-836-2501 Fax: 613-836-2690 • www.middleatlantic.ca
e l e c t r o n i c v e r s i o n a v a i l a b l e a t w w w . m i d d l e a t l a n t i c . c o m
FC-4-1C
MPR raceway mounted modules
interconnect with our unique
genderless connector. Quick and
safe - no hard wiring required!
Summary of Contents for FC-4
Page 2: ......