DOC 4380A
4380A O & M Manual
63
098-00723-000
– Jul 2017 Revision 4.0
SyncSystem 4380A O&M Manual
Power Source has failed; check to ensure the power source is available and connected to the rear
panel of the unit.
Users can also check the current system using the
alarm
and the
status health:power_supply
commands to
check the system status.
4380A> alarm
power_supply:2 -- AC/DC supply missing, or hardware error
4380A>status health:power_supply
[1]
[active] false
[occurrences] 0
[2]
[active] true
[occurrences] 1
[set]
[what] AC/DC supply missing, or hardware error
[when] 2015-08-05-14:26:02.523
[OK] 2015-08-08T14:38:52Z
If the fault condition has cleared, users are able to check the events in the system using the
status
health:power_supply
commands to check on events that occurred earlier.
4380A>status health:power_supply
[1]
[active] false
[occurrences] 0
[2]
[active] false
[cleared]
[what] No errors
[when] 2015-08-06-16:14:38.874
[occurrences] 1
[set]
[what] AC/DC supply missing, or hardware error
[when] 2015-08-05-14:26:02.523
6.4 Outputs Indicator
This indicator provides the status for the NTP Server and system outputs.
This indicator will turn RED if the 4380A detects a hardware fault with one or more of the output modules.
Verify the output modules are locked to reference and the outputs are enabled using the
status
health:outputs_disabled
command and verify both active and occurrences = 0.
4380A>status health:outputs_disabled
[active] false
[cleared]
[what] Outputs are enabled
[when] 2015-08-06-20:51:14.207
[occurrences] 0
[set]
[what] Outputs are disabled
[when] 2015-08-05-14:25:56.817
[OK] 2015-08-08T14:41:32Z
Users can determine which output module(s) has failed:
Based on which systems the 4380A is driving are no longer operating properly
By unplugging the output modules, one at a time, to see which output module was at fault.
Note
: If this does not work there may be more than one output module that failed. Pull them all
and reinsert them one at time to see which one(s) cause a FAULT.
By using the
status health:output_modules
command and/or the
syslog
command and checking
both the active = true and/or occurrences is greater than 0.