5. Troubleshooting
The following are potential issues and recommended solutions when troubleshooting the
MR361 Fiber Optic Encoder Link system. For issues not listed, please contact Micronor Sales.
5.1.
Potential Issues & Solutions
5.1.1. XMTR Power Green LED not ON when controller powered
•
Verify solid electrical connection between wires and screw terminal for both +Uin/+Vin
and GND.
•
Verify that external power supply is rated correctly for the encoder being used and
connected
•
Contact Micronor Sales for further assistance.
5.1.2. RCVR Link Status LED not ON when controller powered
•
Verify solid electrical connection between wires and screw terminal for both +Uin/+Vin
and GND.
•
Verify that external power supply is rated correctly for the drive inputs.
•
Contact Micronor Sales for further assistance.
5.1.3. RCVR Link Status LED Blinks
•
Verify optical link cabling is properly connected and undamaged. A visual fault finder
is an inexpensive tool for verifying continuity.
•
Measure RCVR end of link with an optical power meter. Should read at least -24 dBm.
•
Verify that the entire fiber optic system does not exceed system loss margin
specifications. Use either an optical power meter or OTDR to trace the link.
•
Clean all fiber optic connector surfaces using appropriate cleaning materials.
•
Contact Micronor Sales for further assistance.
5.1.4. RCVR Encoder Outputs not working but both LEDs On
•
If accessible, verify outputs of Encoder using oscilloscope
•
Verify A/B/C/D inputs to XMTR module using oscilloscope
•
Verify A/B/C/D outputs of RCVR module using oscilloscope
•
Contact Micronor Sales for further assistance.