12.6 - RelayCfg (Relay Configuration)
To associate one of the Output Relays to one or more functions: enter the menu “R/W Set”, select “Relay
Cfg”, select the “Relay #” to be programmed, select “Link”; at this stage the list of the available functions is
displayed. Scrolling the list by the “+” and “
-
”
keys the function is selected and then assigned by the key
“Enter”. The assignation is confirmed by the function indication that switches from blinking to steady.
Any of the Output Relays can be programmed to work in two different modes:
N.D.
Normally Deenergized
Relay is energized on trip of the associated functions
N.E.
Normally Energized
Relay is deenergized on trip of the associated functions
Programming of working mode is made as above selecting “OpMode” instead of “Link”.
Display
Description
Setting Range
Relay
Type
Default
Value
Relay1
(R1)
Link
→
T>, tI>, I>>,
tIH, tIo>,
tIo>>, tIoH
Association of functions to
output relay R1
T> - Ta -I> - tI> - I>> - tI>> - IH
–
tIH - Io> - tIo>
- Io>> - So> - tIo>> - tIoH
–
tSo> - BF - RTD
–
IRF
–
CBopen
–
CBclose
–
HwRecov
OpMode
→
N.D.
N.D. (Normally
Deenergized) N.E.
(Normally Energized)
N.D./N.E.
Relay2
(R2)
Link
→
BF
Association of functions to
output relay R2
T> - Ta -I> - tI> - I>> - tI>> - IH
–
tIH - Io> - tIo>
- Io>> - So> - tIo>> - tIoH
–
tSo> - BF - RTD
–
IRF
–
CBopen
–
CBclose
–
HwRecov
OpMode
→
N.D.
N.D. (Normally
Deenergized)
N.E. (Normally Energized)
N.D./N.E.
Relay3
(R3)
Link
→
Ta, I>, I>>,
IH, Io>, Io>>,
IoH
Association of functions to
output relay R3
T> - Ta -I> - tI> - I>> - tI>> - IH
–
tIH - Io> - tIo>
- Io>> - So> - tIo>> - tIoH
–
tSo> - BF - RTD
–
IRF
–
CBopen
–
CBclose
–
HwRecov
OpMode
→
N.D.
N.D. (Normally
Deenergized) N.E.
(Normally Energized)
N.D./N.E.
Relay4
(R4)
Link
→
IRF
Association of functions to
output relay R4
T> - Ta -I> - tI> - I>> - tI>> - IH
–
tIH - Io> - tIo>
- Io>> - So> - tIo>> - tIoH
–
tSo> - BF - RTD
–
IRF
–
CBopen
–
CBclose
–
HwRecov
OpMode
→
N.E.
N.D. (Normally
Deenergized) N.E.
(Normally Energized)
N.D./N.E.
12.7 - Commands
“Commands”
1
st
Control,
to select other available control,
to operate selected control.
Display
Description
Clear
: Erase memory of Trip Counters, Event Records.
Test
: Starts a relay diagnostic test
Reset
: Reset after trip
CBopen
: Manual Open - Close Breaker
CBclose
: Manual Close - Close Breaker
ResThIm
: Reset Thermal Image
12.8 - Info&Ver (Firmware - Info&Version)
The menu displays the Relay Model and the Firmware Version
“
R
eal
T
ime
M
eas”
“Info/Ver”
,
“Model XXXXXX”
,
Model Relay
“
RelayVrs ###.#.#
X
”
,
Firmware Version
to go back to
“Info&Ver”
.
to go back to “
R
eal
T
ime
M