IBEX 8 Nozzle
SMALL FRAME_June 2020
June 20 Page 6 of 41
WATER QUALITY
2.
WATER QUALITY
To obtain the best performance, special consideration should be given to the quality of water used in a MicroCool fog
system. For more information about Water Quality, consult a MicroCool specialist.
MicroCool
IS NOT RESPONSIBLE FOR NOZZLE BLOCKAGE DUE TO POOR WATER QUALITY.
TOTAL DISSOLVED SOLIDS COUNT
Water with total dissolved solids (TDS) counts of greater than 500 parts per million (PPM); water with high calcium
and magnesium carbonate levels, or water with pH levels below 6.7 and above 7.5 may not be satisfactory and could
lead to excessive nozzle blockage and the need for nozzle maintenance.
WATER ANALYSIS
If there is any doubt about water quality, a water analysis is recommended. Of major interest is the water’s Langelier
Saturation Index (SLI) together with other items such as hardness and TDS. A slightly negative, or neutral, Langelier
index is preferred, whereas a positive index may indicate a tendency to form calcium carbonate deposits in the lines
and nozzles. If using city water, an analysis should be available from the city/town water department. If in any doubt,
please contact your MicroCool representative for further information.
WATER TREATMENT
Generally speaking, most municipal water is suitable for atomization. Well water, river water and the like should be
tested before atomizing. If an analysis indicates any unusually high levels of undesirables’ proper treatments are
available. MicroCool
can supply a variety of water treatment systems. Please contact MicroCool
for further
details.
ULTRAVIOLET WATER PURIFIERS
Optional ULTRAVIOLET high intensity light purifiers can also be installed on the inlet water supply to sterilize the
system water. By bombarding the water with UV light, dangerous pathogens, spores and germs are destroyed. UV
systems must be regularly serviced to maintain the correct high intensity output.
REVERSE OSMOSIS WATER TREATMENT
MicroCool offers optional comprehensive reverse osmosis packages for all applications. Units are available for large
scale industrial as well as domestic installations.
Reverse Osmosis units incorporate a semi-permeable membrane that micro-filters the water to 0.0001 microns
removing bacteria, viruses, aqueous salts and metal ions. By eliminating these from the supply water, MicroCool
ensures that clean, hygienic water is used in each system. Clean water will also reduce nozzle blockage, foul odors
and white “chalky” deposits on material close to the fog spray.
MicroCool reverse osmosis systems are designed specifically for each application. Please consult with MicroCool
specialists for more details.
Summary of Contents for IBEX 1000
Page 31: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 31 of 41 IBEX 1 3 GALLON REAR VIEW...
Page 32: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 32 of 41 IBEX 1 3 GALLON RIGHT SIDE VIEW...
Page 33: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 33 of 41 IBEX 1 3 GALLON LEFT SIDE VIEW...
Page 34: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 34 of 41 IBEX 1 3 GALLON TOP VIEW...
Page 35: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 35 of 41 IBEX 1 3 GALLON INTERNAL TOP VIEW...
Page 36: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 36 of 41 IBEX 1 3 GALLON BOTTOM VIEW...
Page 37: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 37 of 41 IBEX 1 3 GALLON 240V CONTROL PANEL...
Page 38: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 38 of 41 IBEX 1 3 GALLON 480V CONTROL PANEL...
Page 39: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 39 of 41 IBEX 1 3 GALLON NOTES 1...
Page 40: ...IBEX 8 Nozzle SMALL FRAME_June 2020 June 20 Page 40 of 41 IBEX 1 3 GALLON NOTES 2...