![Microchip Technology GridTime 3000 Installation Manual Download Page 210](http://html1.mh-extra.com/html/microchip-technology/gridtime-3000/gridtime-3000_installation-manual_1786100210.webp)
• Viewing the LCD main screen
NZST +1200
07:50:15
15 JUL 2021
GNSS NONE
Current Local
Time Zone
Name
Local Time
UTC Offset
(hhmm)
Current Time
and Date
in Local Time
Current Sync Status
(In Sync)
Current Sync Source
(GNSS)
Highest Priority
Active Alarm
(None)
UTC -37
07:50:15
15 JUL 2021
NONE NSYNC
Current Sync Status
(Out of Sync)
Current Sync Source
(None)
Highest Priority
Active Alarm
(Out of Sync
Alarm)
!
Current UTC-TAI leap second offset
(toggle with centre button)
• Performing a SNMP 'get' on the current sync status object (OID .1.3.6.1.4.1.34689.7.1.1.1.1.6)
• Determine if any sync alarms are active — if none are active the unit is in sync
10.2
Test Mode
This section describes how to set the GridTime3000 into test mode, and how to change the time to one selected by
the user.
The Test Mode behaves like an additional sync source, which overrides all other synchronization sources, reports
perfect time accuracy, and can be set to a time specified by the user. While in test mode, the other behavior of the
GridTime 3000 will remain the same. For example, GNSS associated alarms will still trigger based off the physical
inputs to the clock.
Test Mode will be disabled when the GridTime 3000 is power cycled.