9
INVERTER INSTALLATION
INVERTER INSTALLATION
Consider the following when installing the inverter.
6.1
Planning the Installation
Location
•
Install the Inverter indoor in a dry protected location away from any sources of moisture.
•
Find a suitable temperature resistant surface to mount the inverter.
•
Provide enough space for the routing of external wiring, Sub DB board and additional
accessories.
•
The mounting surface must support the weight of the inverter.
•
Exposure to saltwater is particularly destructive.
•
Do not mount the inverter in a closed container.
•
Unrestricted airflow is required for the inverter to operate at optimal efficiency.
•
Ensure a 200mm unrestricted clearance at the top, left and right side of the inverter.
•
Do not install the inverter in the same compartment as non-sealed batteries.
•
Locate the Inverter as close as possible to the batteries in order to keep the battery cables.
as short as possible as supplied with the inverter.
•
If flooded batteries are used, install them in a separate room or compartment.
Orientation
The unit must be mounted in a
“VERTICAL POSITION
” against the wall.
Temperature
Away from sources of high temperature.
Height
Install the inverter so that the display is at eye level.
Fig 6-1: Minimum clearance distances
20cm
Wall
20cm
60-90cm
Cable Trunking
20cm
20cm
Inverter