Parameter
Address
Default
Min
Max
Unit
Logic Diagram
[spacer]
DTOC2: Ineg>> dynamic PSx
076 211
077 211
078 211
079 211
1.00
0.10
8.00
Inom
[spacer]
Setting for operate value Ineg>> dynamic. (Ineg = negative-sequence current)
This operate value is effective only while the timer stage MAIN: Hold time
dyn.param. is elapsing.
[spacer]
DTOC1: Ineg>>> dynamic PSx
076 202
077 202
078 202
079 202
1.00
0.10
8.00
Inom
[spacer]
DTOC2: Ineg>>> dynamic PSx
076 212
077 212
078 212
079 212
1.00
0.10
8.00
Inom
[spacer]
Setting for operate value Ineg>>> dynamic. (Ineg = negative-sequence current)
This operate value is effective only while the timer stage MAIN: Hold time
dyn.param. is elapsing.
[spacer]
DTOC1: tIneg> PSx
076 203
077 203
078 203
079 203
1.00
0.00
100.00
s
[spacer]
DTOC2: tIneg> PSx
076 213
077 213
078 213
079 213
1.00
0.00
100.00
s
[spacer]
Setting for the operate delay of the Ineg> stage.
[spacer]
DTOC1: tIneg>> PSx
076 204
077 204
078 204
079 204
0.50
0.00
100.00
s
[spacer]
DTOC2: tIneg>> PSx
076 214
077 214
078 214
079 214
0.50
0.00
100.00
s
[spacer]
Setting for the operate delay of the Ineg>> stage.
[spacer]
DTOC1: tIneg>>> PSx
076 205
077 205
078 205
079 205
0.50
0.00
100.00
s
[spacer]
DTOC2: tIneg>>> PSx
076 215
077 215
078 215
079 215
0.50
0.00
100.00
s
[spacer]
Setting for the operate delay of the Ineg>>> stage.
[spacer]
DTOC1: IN> PSx
076 054
077 054
078 054
079 054
0.25
0.10
8.00
Inom
[spacer]
DTOC2: IN> PSx
076 164
077 164
078 164
079 164
0.25
0.10
8.00
Inom
[spacer]
Setting for operate value IN>.
[spacer]
DTOC1: IN>> PSx
076 055
077 055
078 055
079 055
Blocked
0.10
8.00
Inom
7 Settings
P631
P631/EN M/R-11-C // P631-310-650
7-111
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......