![Metz Connect EWIO 2 User Manual Download Page 90](http://html.mh-extra.com/html/metz-connect/ewio-2/ewio-2_user-manual_1781387090.webp)
EWIO
2
User Manual
V 1.1 | Stand 10/2020
Seite 90 von 96
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Tel. +49 7702 533-0 | Fax +49 7702 533-433
For additional documentations look at www.metz-connect.com
To test this script, log in to the EWIO
2
and put the content from above into a file named for
example „meas_and ctrl.sh“ in „/usr/bin“ using the vi editor.
Change the permission of the file to 755.
Make sure the digital outputs 1 and 2 are not in manual mode. Set the range of the AI1 to 0-
10 Volt using a GUI client.
Activate the script, how is described in chapter
, and apply different voltages to AI1.
If the applied voltage is lower than 3.5 Volt, the DO1 will be turned on, otherwise turned off.
Increase the voltage over 7.5 Volt; the DO2 will be turned on. If the input voltage falls under
7.5 Volt, the DO2 will be turned off.
11.7.
Sensor IDs for the analog inputs and their meaning
Sensor string Name
enum Unit
Minimum
Maximum
enum Sensor
enum Range
1
"0-10V %"
UNITS_PERCENT
0.0
100.0
ewioSensor_0_10V_Percent
ewioRange_Volt
2
"0-5V % Pullup"
UNITS_PERCENT
0.0
100.0
ewioSensor_0_5V_Percent_PU
ewioRange_Volt_PU
3
"0-10 Volt"
UNITS_VOLTS
0.0
10.0
ewioSensor_0_10V
ewioRange_Volt
4
"0-5 Volt Pullup"
UNITS_VOLTS
0.0
5.0
ewioSensor_0_5V_PU
ewioRange_Volt_PU
5
"Ohm"
UNITS_OHMS
40.0
4E6
ewioSensor_Ohm_2Wire
ewioRange_Ohm_2Wire
6
"User Defined"
UNITS_NO_UNITS
0.0
0.0
ewioSensor_UserDef
ewioRange_Modes ???
7
"PT100"
UNITS_DEGREES_CELSIUS
-50.0
150.0
ewioSensor_PT100
ewioRange_Ohm_2Wire
8
"PT500"
UNITS_DEGREES_CELSIUS
-50.0
150.0
ewioSensor_PT500
ewioRange_Ohm_2Wire
9
"PT1000"
UNITS_DEGREES_CELSIUS
-50.0
150.0
ewioSensor_PT1000
ewioRange_Ohm_2Wire
10
"NI1000-TC5000"
UNITS_DEGREES_CELSIUS
-50.0
150.0
ewioSensor_NI1000_TC5000
ewioRange_Ohm_2Wire
11
"NI1000-TC6180"
UNITS_DEGREES_CELSIUS
-50.0
150.0
ewioSensor_NI1000_TC6180
ewioRange_Ohm_2Wire
12
"BALCO500"
UNITS_DEGREES_CELSIUS
-50.0
150.0
ewioSensor_BALCO500
ewioRange_Ohm_2Wire
13
"KTY81_110"
UNITS_DEGREES_CELSIUS
-50.0
150.0
ewioSensor_KTY81_110
ewioRange_Ohm_2Wire
14
"KTY81_210"
UNITS_DEGREES_CELSIUS
-50.0
150.0
ewioSensor_KTY81_210
ewioRange_Ohm_2Wire