The additional notifications
- System start
- Successful and unsuccessful registration in the web interface
- Successful and unsuccessful authentication for network services
- Software update and
- System error
Can be selected by slide switch.
Only after activating the action field "Save" the settings are applied.
10.5.2.11.
BACnet
In the menu window "BACnet" the required information about the BACnet server is entered.
With the slide switch the BACnet server is activated.
The configuration parameters can be changed in the input fields Device Instance, Device
Name, Device Description and the UDP Port for BACnet IP.
Factory settings are:
For the devices instance : 421000
For the device name : EWIO2_BACnet.
BACnet IP - UDP Port : 47808 (BAC0hex)
For the BACnet Broadcast Management the necessary input fields are
BBMD IP address / host name, BBMD address port and the subscription period.
Factory settings are:
For the BBMD address port : 47808
For the subscription runtime : 1800 s