PAT Appliances & Machines Safety Trainer
AD 3
– MI 3399
215
4.3 Classification of appliances (by protection classes)
According to the design electrical equipment can be divided in three classes. In the table
below the differences between classes are described.
Class
I
II
III
Marking
No marking
Connection to
protection (PE)
conductor of
the installation.
Yes.
All accessible
conductive parts (case
etc.) are connected to
the PE connection.
No.
No connection to mains.
Basic insulation
Performed.
Performed.
Performed / looser limits.
Supplementary
or reinforced
insulation
Not needed in
general.
Needed if there are
accessible unearthed
conductive parts
10
.
Performed.
Not needed.
Supply cord
Three pole (L,N, PE). Can be two pole. Two pole.
Notes
Installation must have
adequate earth
resistance.
Must be supplied from a
SELV (safety low
voltage) source, typically
12 V or 24 V.
Table 4-1: Classification of appliances
4.4 Portable electrical appliances
– measurements
Basic test that need to be conducted while the portabe device is powered off:
1. Visual inspection
2. Earth bond/earth continuity
3. Insulation resistance (with or without Probe)
4. Sub-Leakage (optionaly)
If all conducted test above passed, the portable device should be turned on and the following tests
performed:
1. Leakage (Differential or touch)
2. Polarity
3. PRCD
4. Functional
The probe test is conducted on Class II devices (flatiron, radio with an external antenna,
…)
4.4.1 Visual inspection
Visual inspection of the equipment is intended to confirm that there are no visible signs
of damage or defects. Electrical testing often does not disclose failures that become
apparent on visual inspection. The visual inspection discloses most of faults! A thorough
visual check must be carried out before each electrical safety test.
10
Class I equipment can be combined with class II safety measures!
Summary of Contents for MI 3399
Page 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Page 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Page 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Page 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Page 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Page 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Page 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...