Power Network Application Trainer
– Earthing / Grounding network impedance measurement
66
Figure 46-2: Impulse Measurement example
Notes:
The three-wire method is used for impulse impedance measurement.
During the measurement a current impulse (10/350 μs) is injected into the earth
through a shielded auxiliary probe (H).
Figure 47-2: Typical Impulse shape short-circuit
Impedance of probe H should be as low as possible (to inject higher test current),
Voltage peak is measured between probe S and E,
Use short test lead E, to minimize its influence in the final result,
The current probe resistance Rc and potential probe resistance Rp are measured
using 3-Pole measurement at a fix frequency 3.29 kHz @ 40 Vac open-terminal
test voltage.