![METREL MI 3298 Instruction Manual With Exercises Download Page 64](http://html1.mh-extra.com/html/metrel/mi-3298/mi-3298_instruction-manual-with-exercises_1778927064.webp)
Power Network Application Trainer
– Earthing / Grounding network impedance measurement
64
2.4 Pylon Ground Wire Test (PGWT)
The PGWT measurement is performed to check the overhead grounding wire
connection.
Figure 45-2: Pylon Ground Wire Test (PGWT) example
During the measurement a sinusoidal current Igen is injected into the earth through an
auxiliary probe (H). The resistance of the auxiliary probe (H) should be as low as
possible in order to inject a high-test current. The resistance Rc can be decreased by
using more probes in parallel. A higher injected current improves the immunity against
spurious earth currents.
In the example following current Ig_w is measured according to following equation:
where:
I
g_w
..........Overhead ground wire current
I
gen
..........Generator current (injected test current)
I
f_sum
........Total flex clamp current