Power Network Application Trainer
– Earthing / Grounding network impedance measurement
109
Previous exercises describe the measurement procedure with one flex-clamp and step
by step measurement (example 2), following exercises will show procedure using one
flex-clamp but measuring of two foots together and all four foots in one step.
4.1.3.5.1 S
– Flex measuring method by using one Flex-clamp with
simulated
regular pylon’s foot condition and resistance
earth character
– measuring of two foots together
Figure 71-2: S-
Flex measurement setup for measuring two pylon foot’s
Switch position Simulated condition
Application
Expected result
Regular measurement place
condition (simulated resistive earth
character), flex measurement,
simulated ground wire connection
Pylons (mono and multi-leg)
with and without protective earth
cable connection
Ski lifts
Radio towers
Foot Nm. 1& 2 approx. 6,27 Ω
Foot Nm. 3 & 4 approx. 4,61 Ω
Z
tot calc
= 2,65 Ω
Table 32-2:
S-Flex measurement setup/result presentation
Measuring procedure
1. Follow the measurement setup connection described under 4.1.3.1 exercise. Connect
setup switches and ground wire accordingly. Take care that flex-clamp will be installed
around two pylon legs (around 1&2 in the first measurement and around 3&4 in the
second step).
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...