MI 3109 EurotestPV Lite
Measurements
35
R LOWΩ measurement procedure
Select continuity function using the function selector keys.
Set sub-function to
R LOWΩ
using
/
keys.
Enable and set
limit
(optional).
Connect
PV continuity test lead to the instrument.
Compensate
the test leads resistance (if necessary, see
section 5.2.3
Connect
the test leads to the appropriate PE wiring (see Figure 5.6).
Press the
TEST
key to perform the measurement.
After the measurement is finished
store
the result by pressing the
MEM
button
(optional).
Figure 5.7: Example of RLOW
Ω result
Displayed result:
R................R LOWΩ resistance
R+..............result at positive polarity
R-...............result at negative test polarity
U:.............. actual voltage on test inputs
5.2.2 Continuous resistance measurement with low current
In general, this function serves as standard
-meter with a low testing current. The
measurement is performed continuously without polarity reversal. The function can also
be applied for testing continuity of inductive components.
Connection for continuous resistance measurement
Figure 5.8: Example of Continuity test
Continuous resistance measurement procedure
Select continuity function using the function selector keys.
Set sub-function to
CONTINUITY
using
/
keys.
Enable and set the
limit
(optional).