background image

Preliminary—This information may change.

Miscellaneous—Emergency Stations (AFAWS-Series)    

9

Assembly of Units with
Armored Cable Handsets

This assembly procedure is for telephones with armored cable handsets.
Complete the following steps when the enclosure has been mounted and
the system wiring is in place (refer to Figure 3).
1.

 

Attach system wiring to the terminal strip on the telephone chassis
assembly. See Figure 2 or 3.

2.

 

Install 6-32 nut in backbox. Do not tighten.

3.

 

Inset armored cable end into slot on top of telephone chassis assembly.

4.

 

Install telephone chassis assembly in backbox.

5.

 

Install trim ring on backbox with 6-32 wing nuts. Do not tighten.

Notes: Telephone circuits are supervised and power-limited.

Use twisted pair shielded cable for telephone circuit wiring. For
best operation, terminate shield at FFT-7/S 24V power supply
common (-).
Maximum telephone circuit wire resistance is 40 ohms.
For ELR connection to devices with terminals, use Resistor 71252.
For ELR connection to devices with flying leads, use
Resistor 71245. In Canada, N-ELR Resistor Assembly is required.
Refer to the fire panel manual for UL power-limited requirements
and further information.

Summary of Contents for AFAWS FFT-7

Page 1: ...e 0399 1999 Johnson Controls Inc 1 Code No LIT 445215 www johnsoncontrols com Preliminary This information may change General Background 3 System Wiring 5 Assembly of Units with Coiled Cord Handsets 7 Assembly of Units with Armored Cable Handsets 9 Emergency Telephone Stations AFAWS Series ...

Page 2: ...Preliminary This information may change 2 Miscellaneous Emergency Telephone Stations AFAWS Series ...

Page 3: ...mpatible with the FFT 7 and FFT 7S master telephone stations The series has a handset with a push to talk switch a hearing aid compatible speaker and an indicator that illuminates when the warden station is connected to the master telephone station Up to seven handsets including the master handset may be operated simultaneously AFAWS components are illustrated in Figure 1 ...

Page 4: ...le Coiled Cord AFAWS TELC AFAWS TELA Tempered Glass Hammer Backbox AFAWS BX BRKG N Surface Mounting Flush Mounting AFAWS LS AFAWS LR Flush Mounting Surface Mounting AFAWS KS AFAWS KR Firefighter s Telephone Firefighter s Telephone Firefighter s Telephone Firefighter s Telephone Figure 1 AFAWS Series Components ...

Page 5: ...m Wiring Telephone system wiring from the FFT 7 FFT 7S through the control point such as the XPM 8 to the warden s station must not be connected to or run in the same conduit or cable tray as Signal Alarm Circuits SLCs speaker circuits strobe circuits cable TV or other noise producing circuits ...

Page 6: ...Preliminary This information may change 6 Miscellaneous Emergency Telephone Stations AFAWS Series ...

Page 7: ...ssembly in backbox 4 Install trim ring on backbox with 6 32 wing nuts Do not tighten 5 Install door assembly 6 Tighten wing nuts Notes Telephone circuits are supervised and power limited Use twisted pair shielded cable for telephone circuit wiring For best operation terminate shield at FFT 7 S 24V power supply common Maximum telephone circuit wire resistance is 40 ohms For End of Line Resistor ELR...

Page 8: ...g Tip Activated Polarity Telephone Loop IN SLC Control Module Wiring XPC 8 AFAWS Series Telephone Activated Polarity Shown Telephonic Loop In In In In Out Out Out Out Optional 4 wire Return Class A Connection Omit R 47K Resistor Up to six external telephone handsets may be connected to one FFT 7 S Maximum line resistance from FFT 7 S to farthest telephone must not exceed 40 ohms P2 16 15 14 13 12 ...

Page 9: ... cable end into slot on top of telephone chassis assembly 4 Install telephone chassis assembly in backbox 5 Install trim ring on backbox with 6 32 wing nuts Do not tighten Notes Telephone circuits are supervised and power limited Use twisted pair shielded cable for telephone circuit wiring For best operation terminate shield at FFT 7 S 24V power supply common Maximum telephone circuit wire resista...

Page 10: ...ephone Circuits Telephone Power Polarity from FFT 7 S A B C D E F G H SPEAKER CIRCUITS SPEAKER CIRCUITS A B C D Figure 3 AFAWS Series Telephone to VCM 4 Circuit Connections Notes Telephone circuits are supervised and power limited Twisted pair shielded cable should be used for telephone circuit wiring For best operation terminate shield at FFT 7 S 24V power supply common Maximum telephone circuit ...

Page 11: ...Preliminary This information may change Miscellaneous Emergency Stations AFAWS Series 11 Notes ...

Page 12: ...n may change 12 Miscellaneous Emergency Telephone Stations AFAWS Series Notes Controls Group www johnsoncontrols com 507 E Michigan Street FAN 445 P O Box 423 Fire Management Accessories Manual Milwaukee WI 53201 Printed in U S A ...

Reviews: