Mixer 1 settings
→
Mixer room therm.
=
0.
If an ecoSTER TOUCH room panel is
connected, also temporarily set the Room
temperaturę factor = 0.
Guidelines for proper setting
of the heating curve:
- floor heating
0,2 -0,6
- radiator heating 1,0 - 1,6
- boiler
1,8 - 4
Guidelines for selection of appropriate
heating curve:
- if the outdoor temperature drops, and the
room temperature increases, the selected
heating curve value is too high,
- if the outdoor temperature drops, and the
room temperature drops as well, the selected
heating curve value is too low,
- if during frosty weather the room
temperature is proper, but when it gets
warmer - it is too low, it is recommended to
increase the
Curve translation
and to select a
lower heating curve,
- if during frosty weather the room
temperature is too low, and when it gets
warmer - it is too high, it is recommended to
decrease the
Curve translation
and to select
a higher heating curve.
Buildings with poor thermal insulation require
higher heating curves, whereas for buildings
which have good thermal insulation, the
heating curve can have lower value.
The regulator can increase or decrease the
preset temperature, calculated in accordance
with the heating curve, if it exceeds the
temperature range for the given circuit.
8.16
Description of night time decrease
settings
Boiler night time decreases
The boiler operates in selected time
intervals. Outside of the selected intervals,
the boiler is burned off.
Night time decreases for heating
circuits, HUW container and circulation
pump operation.
The intervals can be used to define time
periods at which lower preset temperature
may be set e.g. for a night time or when the
user is not at home (e.g. he/she left for a
work/school). This feature enables automatic
reduction of preset temperature without
compromising the heat comfort and reduces
fuel consumption.
To
activate
time intervals,
set
the
parameter:
Night time decrease
for the given
heating circuit to ON.
Night time decrease may be set for working
days, Saturdays and Sundays.
The example of night time decrease of preset
temperature from 22:00 to 06:00 next day
and from 09:00 to 15:00 is given below.
Note! Setting of time intervals for
24 hours (one day) should start
from 00:00!