Metal-Fach ecoMAX860P TOUCH Operating Manual Download Page 37

37 

 

Max. HUW temperature 

It  requires  a  HUW  sensor  to  be  plugged  in.  This  parameter  decides  on 
which  maximum  temperature  will  the  HUW  container  be  heated  during 
dropping  down  excessive  heat  in  alarm  states.  It  is  a  crucial  parameter 
because  setting  this  for  too  high  value  can  lead  to  the  risk  of  users 
scalding  with  utility  water.  On  the  other  hand,  too  low  value  of  this 
parameter  can  lead  to a situation,  when  during  boiler  overheating  there 
will  be  no  possibility  to  drop  down  excessive  heat  into  the  HUW  tank. 
When projecting the HUW installation, there should be an assumption of 
controller malfunction. This situation can lead to dangerous level of HUW 
temperature,  leading  to  user  scalding.  It  is  advised  to  use  additional 
security precautions in form of thermostatic values.  

Increase boiler temp. from HUW 
and Mixer 

This parameter determines the increase of the set boiler temperature in 
order  to  load  the  HUW  tank,  buffer,  and  the  mixer  circuit.  The 
temperature is only increased when there is a need to do so. When the 
set temperature of the boiler is on a satisfactory level, the regulator will 
not change it in order to load the HUW tank, buffer, or mixer circuit. The 
increase of the set boiler temperature for the period of loading the HUW 
tank is signalled with the letter “C” in the main window of the display. 

HUW operation extension 

Available  after  connecting  a  HUW  sensor.  When  the  HUW  tank  is  fully 
loaded and the HUW pump is switched off, the boiler may be in danger 
of  overheating.  This  occurs  when  the  set  HUW  temperature  is  higher 
than  the  set  boiler  temperature.  The  problem  is  particularly  prominent 
when  the  HUW  pump  works  in  “SUMMER”  mode  and  the  CH  pump  is 
deactivated.  In order  to cool  the  boiler  down,  the  HUW pump  operation 
can be extended by the 

HUW operation extension  time 

value. 

Circulation pump standstill time 

It  is  the  time  between  periods  of  circulation  pump  operation  and  it  is 
defined  by  the  parameter 

circulation  standstill  time 

(recommended 

setting  is  between  15-40  min.)  The  circulation  pump  is  operating  in 
cycles for the time of 

circulation operation time

 (recommended setting is 

between 60 and 120s.) 

Circulation pump operation time 

CH pump working mode 

Available  options:  OFF  =  no  support  boiler  pump;  ON  =  boiler  pump 
works  normally;  shunt  pump  =  boiler  pump  works  as  shunt  pump;  heat 
exchanger  =  boiler  pump  works  continuously  in  a  short  circuit  boiler  - 
exchanger. 

CH pump standstill time by 
thermostat 

When  the  temperature  of  the  heated  rooms  is  reached  (the  contact  of 
the room thermostat is open), the CH pump is stopped for the 

CH pump 

standstill  time  from  the  thermostat

,  after  which  the 

CH  pump  operation 

time  from  the  thermostat 

is  activated.

 

Note:  The  following  conditions 

must be met in order to stop the pump via the room thermostat: 

 

Boiler room thermostat selection 

≠ deactivated

 

Pump Off by thermostat 

YES

 

CH pump activation time by 
thermostat 

Circulation pump starting 
temperature 

The temperature at which the circulation pump is activated. 

14.4

 

BUFFER 

 

Buffer support 

This  parameter  is  used  to  turn  on  operation  with  the  buffer.  It  is 
available  after  connecting  an  additional  B  module  and  buffer 
temperature sensors. 

Loading start temperature 

The  parameter 

Loading  start  temperature

  defines  the  upper  buffer 

temperature  below  which  the  process  of  buffer  loading  is  being 
started.  This  process  will  then  be  finish  when  the  bottom  buffer 
temperature will reach defined temperature in the parameter 

Loading 

stop temperature.

 

Loading stop temperature 

Heat start installation 

If the top buffer temperature drops below this value, in order to save 
electrical  power,  the  mixer  pumps  and  HUW  pumps  will  be 
deactivated.  This  function  is  particularly  useful  when  working  in 
GRATE mode. 

14.5

 

 MIXER 

 

Mixer support

 

  Off 

The mixer actuator and pump are not in operation. 

  CH On 

It  is  being  used  when  a mixing  circuit is loading  a  heat  installation  of 
CH. The maximum mixing circuit temperature is not being limited, the 
mixer  is  fully  opened  during  alarms  e.g.  with  boiler  overheating. 
Attention:  do  not  use  this  option  when  the  heat  installation  is  made 
with  pipes  not  resistant  for  high  temperatures.  In  such  cases  it  is 
recommended to set the mixer operation for FLOOR switched on. 

Summary of Contents for ecoMAX860P TOUCH

Page 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Page 2: ......

Page 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Page 6: ...6...

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Page 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Page 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Page 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Page 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Page 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Page 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Page 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Page 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Page 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Page 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Page 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Page 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Page 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Page 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Page 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Page 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Page 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Page 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Page 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Page 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Page 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Page 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Page 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Page 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Page 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Page 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Page 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Page 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Page 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Page 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Page 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Page 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Page 43: ......