Return protection

 

 

 

Return protection 4D 

This parameter turns on/off the boiler return protection function, which is 
being done by mixing valve together with electric actuator. Attention: do 
not activate this function when there is no actuator installed on the valve! 

 

Return histeresis 

The  electric  actuator  will  return  to  its  normal  operation  with

  return 

temperature ≥ min. return tempe return hysteresis.

 

 

Min. set return temperature 

The boiler return temperature below which the electric actuator will close 
the mixing valve.  

 

Valve closing percentage 

It is a value for opening the mixing valve during active return protection 
function.  This  value  is  given  in  percentage.  This  value  should  be  set  in 
such  way,  that  the  return  temperature  can  raise.  Attention:  the  return 
protection function will work only in case when the set boiler temperature 
will  be  set  on  sufficiently  high  value,  otherwise  there  will  be  too  many 
lock ups of the actuator. Attention: The valve is locking up with the +-1% 
of precision. 

 

Temperature shunt pump 
activation 

The temperature at which the shut pump is activated. 

Thermostat select 

The following options are available:  
Off 

(deactivates  the  effect  of  the  room  thermostat  on  the  boiler’s 

operation) 
Universal  (enables  a  NO-NC  room  thermostat  on  terminals  42-43, 
recommended for thermostats with hysteresis below 1K) 
ecoSTER  (this  option  is  available  when  the  ecoSTER  TOUCH  room 
panel is connected, the signals on the status of the thermostat are sent 
from the room panel) 

Min. boiler temp. 

Minimal set temperature for the boiler, that can be edited by the user in 
user menu and also a minimal temperature, that can be automatically set 
by a controller e.g. from night decrease, weather control etc.  

Max. boiler temp. 

Maximal set temperature for the boiler, that can be edited by the user in 
user  menu  and  also  a  maximal  temperature,  that  can  be  automatically 
set by a controller e.g. from night decrease, weather control etc. 

Reserve boiler 

Determines  pellet  boiler  temperature  below  which  reserve  boiler  is 
activated  (i.e.  gas  boiler).  Setting  "0”  value  causes  deactivation  of 
reserve  boiler  control  and  switching  joint  number  43-44  on  alarms 
service. 

Alarms 

Allows for definition of alarm number or group of alarms after which exit 
number  46-47  is  connected.  In  order  for  alarms  to  connect  exit, 
parameter RESERVE BOILER must be set for value "0”. 

Boiler cooling temp. 

Preventive  boiler  cooling  temperature.  When  this  temperature  is 
exceeded,  the  regulator  switches  on  the  hot  usable  water  pump  and 
opens  the  mixer  circuits  in  order  to  cool  the  boiler  down.  The  regulator 
will  turn  the  hot  usable  water pump  when  the  temperature of  this  water 
exceeds the maximum value. The regulator will not open the mixer circuit 
when 

mixer support = floor On

.

 

Parameter A,B,C FL 

Parameter  is  related  with  automatic  power  modulation  of  boiler  by 
stabilizing the preset boiler temperature. The bigger the value the bigger 
increase  in  power  of  the  boiler.  Too  big  value  can  cause  instability  of 
sustaining the preset boiler temperature. 

 

14.3

 

CH and HUW 

 

CH pump activation temperature 

This parameter decides on the temperature of boiler pump activation. It 
secures the boiler against retting, that can occur when the boiler is being 
cooled down with cold water from the installation. Attention: deactivation 
of  boiler  pump  doesn’t  guaranteed,  that  the  boiler  is  secure  against 
retting  and  therefore  corrosion.  It  is  recommended  to  apply  additional 
automatics e.g. 4-way valve or 3-way thermostatic valve. 

CH pump standstill when loading 
HUW 

It  requires  a  HUW  sensor  to  be  plugged  in.  A  prolonged  HUW  tank 
loading can, with HUW priority activated, lead to excessive cooling down 
of  CH  installation,  because  with  these  kind  of  settings  the  CH  pump  is 
switched  off.  The  parameter  of  pause  time  of  CH  pump  preventing  this 
by  periodic  operation  of  CH  pump  while  HUW  tank  loading.  The  CH 
pump will after this time activate for fixed set time of 30s. 

Min. HUW temperature 

It requires a HUW sensor to be plugged in. This parameter can be used 
for  limitation  of  possibility  to  choose  too  low  value  of  HUW  set 
temperature. 

Summary of Contents for ecoMAX860P TOUCH

Page 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Page 2: ......

Page 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Page 6: ...6...

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Page 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Page 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Page 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Page 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Page 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Page 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Page 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Page 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Page 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Page 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Page 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Page 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Page 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Page 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Page 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Page 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Page 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Page 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Page 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Page 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Page 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Page 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Page 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Page 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Page 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Page 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Page 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Page 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Page 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Page 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Page 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Page 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Page 43: ......

Page 44: ...19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plumelectronics eu Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfac...

Reviews: