Connecting emission sensor: 1 – exhaust temp.
sensor type CT2S, 2 – sensor lead, 3 – flue.
Caution: Opening the boiler door
can
cause
the
emission
temperature
to
exceed
the
sensor‘s
thermal
resistance,
which can burn the sensor out.
12.9
Checking temperature sensors
Temperature sensors CT4/CT6-P/CT2S can
be checked by measuring their resistance at
the given temperature. In the case of finding
significant differences between the value of
measured
resistance
and
the
values
presented in the table below, the sensor
must be changed.
CT4 (KTY81)
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
802
815
828
10
874
886
898
20
950
961
972
25
990
1000
1010
30
1029
1040
1051
40
1108
1122
1136
50
1192
1209
1225
60
1278
1299
1319
70
1369
1392
1416
80
1462
1490
1518
90
1559
1591
1623
100
1659
1696
1733
CT6-P (PT1000) – weather
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
-25
901,6
901,9
1000,2
-20
921,3
921,6
921,9
-10
960,6
960,9
961,2
0
999,7
1000,0
1000,3
25
1096,9
1097,3
1097,7
50
1193,4
1194,0
1194,6
100
1384,2
1385,0
1385,8
125
1478,5
1479,4
1480,3
150
1572,0
1573,1
1574,2
CT2S (PT1000) - exhaust
Temp.
°C
Min.
Ω
Nom.
Ω
Max.
Ω
0
999,7
1000,0
1000,3
25
1096,9 1097,3
1097,7
50
1193,4 1194,0
1194,6
100
1384,2 1385,0
1385,8
125
1478,5 1479,4
1480,3
150
1572,0 1573,1
1574,2
12.10
Connection of mixers room
thermostat
Room
thermostat
connected
to
the
operational unit affects mixer 1 circuit and/or
boiler circuit. If the whole heating circuit of
the building is supplied by a mixer with
electric servo, room thermostat for boiler
should be turned off.
Room thermostat, after disconnection of its
connectors reduces preset temperature of
the mixer circuit by a value set up in: Reduce
preset mixer temp. to thermostat. This
parameter is available in:
Mixer 1-4 settings
The mixer pump does not stop upon opening
contacts of the room thermostat unless other
settings have been made in the Service
Menu. Select the value of this parameter so
that once the room thermostat has
responded (its contacts have opened), the
temperature in the room drops.