Metal-Fach ecoMAX860P TOUCH Operating Manual Download Page 15

15 

 

set  the  decrease  by  3°C  from  22:00  to 
23:59. 

 

Time  interval  is  disregarded  when 
its  decrease  is  set  to  "0"  even 
though  "from...  to  ..."  values  have 
been entered. 

8.19

 

Fuel level setup 

 
Activating the fuel level gauge 

In  order  to  enable  display  of  the  fuel  level, 
set value of parameter 
Boiler settings 

Fuel level 

 Alarm level 

to  a  value  greater  than  zero,  e.g.  10%.  By 
pressing  the  right  or  left  box  in  the  main 
window  you  can  select  the  fuel  level 
indicator. Fuel level can also be displayed on 
the ecoSTER TOUCH room panel. 
 
Operation of fuel level indicator 
Any  time  upon  filling  fuel  tank,  press  and 
hold  pressed  current  fuel  level  value. 
Following prompt appears: 

 

"Set  fuel  level  at  100%  Once  selected  and 
confirmed YES, fuel level is set at 100%. 
Once  selected  and  confirmed  YES,  fuel  level 
is set to 100%. 
Note:  Fuel  may  be  replenished  at  any  time 
without  a  need  to  wait  for  complete  empty 
fuel  tank.  Replenish  fuel  always  to  the  level 
corresponding to 100% level of the fuel tank 
and set 100% level as described above.  
 
Description of operation 
The regulator calculates the fuel level basing 
on  the  current  fuel  consumption.  Default 
settings  do  not  always  correspond  to  the 
actual  consumption  of  fuel  by  the  given 
boiler,  therefore,  for  proper  operation  this 
method  requires  the  regulator  user  to 

perform  level  calibration.  No  additional  fuel 
level sensors are required. 
 
Calibration  
To  perform  calibration  -  fill  the  fuel  tank  to 
the  level  corresponding  to  its  full  load  and 
set the parameter: 
Boiler settings 

 Fuel Level 

→ 

Fuel level 

calibration 

 Fuel Level 100% 

The indicator in the main window will be set 
to  100%.  On-going  calibration  process  is 
signalled  by  flashing  fuel  level  gauge.  The 
gauge will flash until the time of marking the 
point  corresponding  to  minimal  fuel  level. 
One 

must 

systematically 

control 

the 

decreasing level of fuel in the bin. When the 
level  reaches  the  requested  minimum,  set 
the value of the parameter: 
Boiler settings 

 Fuel Level 

→ 

Fuel level 

calibration 

 Fuel Level 0% 

Calibration  can  be  skipped  if  the  Feeder 
Efficiency
 and Tank capacity, parameters are 
set  correctly  in:  Menu 

  Service  settings 

 Burner settings 

→ 

Operation 

8.20

 

Information 

Information"  menu  allows  to  preview 
temperatures  being  measured  and  to 
recognize which equipment is currently ON.  

 

Upon 

connection 

of 

mixers' 

extension 

module, 

information 

windows  of  additional  mixers  are 
displayed. 

8.21

 

Manual control 

Regulator offers possibility to manual start of 
working  equipment  such  as  pump,  feeder 
motor  or  fan.  This  feature  enables  checking 
whether  the  given  equipment  is  fault-free 
and properly connected 

 

Note:  Access  to  manual  control 
menu is possible only in the STAND-
BY  mode,  i.e.  when  the  boiler  is 
OFF. 

 

Note:  Long-term  operation  of  the 
fan,  the  feeder  or  other  working 
equipment  may  lead  to  occurrence 
of hazardous conditions. 

8.22

 

 Grate 

Summary of Contents for ecoMAX860P TOUCH

Page 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Page 2: ......

Page 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Page 6: ...6...

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Page 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Page 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Page 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Page 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Page 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Page 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Page 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Page 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Page 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Page 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Page 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Page 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Page 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Page 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Page 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Page 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Page 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Page 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Page 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Page 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Page 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Page 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Page 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Page 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Page 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Page 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Page 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Page 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Page 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Page 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Page 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Page 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Page 43: ......

Page 44: ...19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plumelectronics eu Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfac...

Reviews: