Metal-Fach ecoMAX860P TOUCH Operating Manual Download Page 13

13 

 

Settings  for  mixer  with  weather  sensor 
without 

room 

thermostat 

ecoSTER 

TOUCH 
Set  parameter  Mixer  weather  control  to  On
Select  weather  curve.    Using  parameter 
Curve 

translation

set 

preset 

room 

temperature following the formula: 
Preset  room  temperature  =  20°C  +  heating 
curve translation.  
In this setup, it is possible to connect a room 
thermostat which will equalize the inaccuracy 
of  selecting  heating  curve,  if  the  selected 
heating curve value is too high. In such case, 
it  is  necessary  to  set  the  value  of  preset 
mixer  temperature  decrease  by  thermostat, 
e.g. at 2°C. After opening of the thermostat 
contacts, 

the 

preset 

mixer 

circuit 

temperature  will  be  decreased,  which,  if 
proper  decrease  value  is  selected,  will  stop 
growth of temperature in the heated room.  
 
Settings  for  mixer  with  weather  sensor 
and with room thermostat  
Set  parameter  Mixer  weather  control  to  On
Select  weather  curve.  The  room  panel 
automatically  translates  the  heating  curve, 
depending  on  the  preset  room  temperature. 
The  regulator  relates  the  setting  to  20°C, 
e.g.  for  preset  room  temperature  =  22°C, 
the regulator will translate the heating curve 
by 2°C, for preset room temperature = 18°C, 
the regulator will translate the heating curve 
by -2°C.

 

In some cases it may be necessary 

to fine-tune the heating curve translation. 
In  this  setup,  the  ecoSTER  TOUCH  room 
thermostat can: 
- decrease the heating cycle temperature by 
a  constant  value  when  the  preset  room 
temperature  is  reached.  Analogously,  as 
specified  in  the  previous  point  (not 
recommended), or 
-  automatically,  continuously  correct  the 
heating cycle temperature.  
It is not recommended to use both options at 
the same time.  
Automatic correction of room temperature is 
carried  out  in  accordance  with  the  following 
formula: 
Correction  =  (Preset  room  temperature  - 
measured  room  temperature)  x  room 
temperature coefficient /10  
 

Example:  
Preset  temperature  in  the  heated  room  (set 
at  ecoSTER  TOUCH)  =  22°C.  Temperature 
measured  in  the  room  (by  ecoSTER  TOUCH) 
= 20°C. Room temp. factor. = 15. 
Preset  mixer  temperature  will  be  increased 
by (22°C - 20°C) x 15/10 = 3°C. 
It  is  necessary  to  find  appropriate  value  of 
the  Room  temp.  factor.  The  higher  the 
coefficient,  the  greater  the  correction  of 
preset  boiler  temperature.  If  the  setting  is 
“0”,  the  preset  mixer  temperature  is  not 
corrected. Note: setting a value of the room 
temperature  coefficient  too  high  may  cause 
cyclical fluctuations of the room temperature! 

8.17

 

Weather controlled 

Depending  on  the  temperature  measured 
outside  the  building,  both  preset  boiler 
temperature  and  temperatures  of  mixer 
circuits  can  be  controlled  automatically.  If 
proper  heating  curve  is  selected,  the 
temperature  of  the  circuits  is  calculated 
automatically,  depending  on  the  outdoor 
temperature.  Thus,  if  the  selected  heating 
curve  is  appropriate  for  the  given  building, 
the room temperature stays more or less the 
same, regardless of the temperature outside.  
Note:  during  trial  and  error  selection  of 
appropriate  heating  curve,  it  is  necessary  to 
exclude influence of the room thermostat on 
regulator  operation  (regardless  of  whether 
the room thermostat is connected or not), by 
setting the parameter: 
Mixer 1 settings 

 Mixer room therm. = 

0. 
If  a  room  panel  ecoSTER  TOUCH  is 
connected,  it  is  also  necessary  to  set  the 
parameter Room temperature factor = 0. 
 
Guidelines  for  proper  setting  of  the  heating 
curve: 

 

floor heating 

 

0,2 -0,6 

 

radiator heating 

 

1,0 - 1,6 

 

boiler 

 

 

1,8 - 4  

Summary of Contents for ecoMAX860P TOUCH

Page 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Page 2: ......

Page 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Page 6: ...6...

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Page 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Page 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Page 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Page 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Page 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Page 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Page 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Page 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Page 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Page 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Page 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Page 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Page 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Page 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Page 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Page 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Page 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Page 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Page 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Page 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Page 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Page 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Page 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Page 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Page 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Page 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Page 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Page 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Page 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Page 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Page 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Page 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Page 43: ......

Page 44: ...19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plumelectronics eu Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfac...

Reviews: