Metal-Fach ecoMAX860P TOUCH Operating Manual Download Page 12

12 

 

 

set  HUW  priority,  using  the  Priority 
parameter - in this case, the CH pump is 
deactivated  to  speed  up  filling  of  the 
HUW tank. 

 

set simultaneous operation of the CH and 
HUW pump, using parameter No priority

8.11

 

Setting HUW preset  

temperature 

Preset  HUW  temperature  is  defined  by 
parameter:  
HUW settings 

 HUW preset temp. 

8.12

 

HUW container hysteresis 

Below  HUW  preset  temp.  –  HUW  container 
hysteresis
 starts HUW pump to load the HUW 
container. 

 

After setting a low hysteresis value, 
HUW  pump  will  run  faster  when 
HUW temperature falls. 

8.13

 

HUW circulation 

The settings can be found in: 
HUW  Settings 

→ 

Schedule  -  circulation 

pumps  
and 
Service settings 

→ 

CH and HUW settings  

Setting  of  circulating  pump  control  is 
analogical  to  night  decrease  setting. 
Circulating  pump  switches  on  in  selected 
time  intervals.  In  disregarded  time  intervals 
circulating  pump  will  start  and  remain  in 
operation  for  the  period  of  time  set  in 
Circulating  pump  operation  time  ,  then  will 
stop  and  remain  out  of  operation  for  the 
period  of  time  set  in  Circulating  pump 
standstill time

8.14

 

Enabling the SUMMER function 

In  order  to  activate  the  SUMMER  function, 
which  enables  to  load  the  HUW  tank  in  the 
summer, without the need  for activating the 
CH  system  and  mixer  cycles,  set  the 
parameter SUMMER mode to Summer. 
Summer/Winter 

 SUMMER mode 

 

In  Summer  mode,  all  heat 
receivers  may  be  shut  off,  so 
before  enabling  it  please  make 
sure  that  the  boiler  does  not 
overheat. 

If  the  weather  sensor  is  connected  SUMMER 
function  can  be  activated  automatically  with 
the  Auto  parameter  including  settings  for 
SUMMER  mode  act.  temperature,  SUMMER 
mode deact. temperature
.  

8.15

 

Disinfection HUW container 

The  regulator  has  a  function  of  automatic, 
periodic heating of HUW container to 70°C to 
eliminate  bacterial  flora  from  the  HUW 
container.  

 

Keep  the  tenants  informed  of 
activating  the  disinfection  function 
as  there  is  risk  of  being  burnt  with 
hot usable water. 

The  regulator  increases  the  HUW  container 
temperature  once  a  week,  at  2:00  a.m. 
Monday. After 10 minutes of maintaining the 
temperature  at  70°C,  the  HUW  pump  is 
switched off and the boiler returns to normal 
operation.  Do  not  activate  the  disinfection 
function when the HUW support is off. 

8.16

 

Mixer circuits settings 

Settings  for  the  first  mixer  circuit  can  be 
found in the menu: Mixer 1 settings 
Settings for other mixers can be accessed in 
next  menu  items  and  they  are  identical  for 
each circuit. 
 
Settings  for  mixer  without  weather 
sensor
 
It  is  necessary  to  manually  set  the  required 
water  temperature  in  the  heating  mixer 
circuit  using  parameter  Preset  mixer  temp.
e.g.  at  a  value  of  50°C.  The  value  should 
allow 

to 

obtain 

the 

required 

room 

temperature. 
After  connecting  room  thermostat,  it  is 
necessary  to  set  a  value  of  decrease  in 
preset  mixer  temperature  by  thermostat 
(parameters Mixer room therm.) e.g. at 5°C. 
This  value  should  be  selected  by  trial  and 
error.  The  room  thermostat  can  be  a 
traditional  thermostat  (NO-NC),  or  room 
panel  ecoSTER  TOUCH.  Upon  activation  of 
the  thermostat,  the  preset  mixer  circuit 
temperature  will  be  decreased,  which,  if 
proper  decrease  value  is  selected,  will  stop 
growth of temperature in the heated room.  
 

Summary of Contents for ecoMAX860P TOUCH

Page 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Page 2: ......

Page 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Page 6: ...6...

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Page 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Page 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Page 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Page 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Page 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Page 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Page 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Page 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Page 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Page 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Page 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Page 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Page 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Page 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Page 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Page 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Page 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Page 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Page 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Page 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Page 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Page 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Page 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Page 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Page 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Page 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Page 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Page 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Page 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Page 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Page 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Page 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Page 43: ......

Page 44: ...19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plumelectronics eu Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfac...

Reviews: