merten 683729 Quick Start Manual Download Page 1

As at 09/02

1

 Chapter 1: System components

1.1

 

Power supplies

 Power supply 2x320 REG-K

Art. no. 683729

Power supply 2x320 REG-KChapter 1:System componentsArt. no.683729As at 09/021.1Power supplies

1.

Function  

1

2.

Installation  

1

3.

Technical Data 

 2

4.

Settings in the EIB Tool Software (ETS) 

 3

The power supply 2x320 REG-K makes the energy 
available for the bus devices on two lines. The device 
has two integrated chokes which isolate the data tele-
grams from the power supply.  The bus voltage can be 
picked up via a bus connecting terminal. A data rail is 
not required. The power supply (PS) provides a stabi-
lised safety extra-low voltage (SELV) of DC 29 V ± 1 V. 
The max. output current is 320 mA per line.

If the bus devices are evenly distributed on the line, it 
is possible to operate up to 64 bus devices on one line. 
The max. cable length between the power supply and 
the furthest bus device is 350 m.

Two slide switches are located under the hinged cover 
next to the bus connecting terminals. In the "RESET" 
position, the connected bus devices for each line are 
reset. This state is indicated by a red LED (RESET) on 
the device.

|

The disconnection of a line (RESET) should be 
retained for at least 30 seconds.

The bus votlage is connected by setting the slide 
switches to the "ON" position. The green LED (RUN) in-
dicates that the power supply is ready for operation.

If the output current is too high, the red overcurrent 
LEDs (I>I

max

) light up or flash. In the event of a short cir-

cuit between the red and black conductors of the bus 
cable, the green LEDs (RUN) are extinguished or flash.

|

Once the short circuit has been rectified, the 
power supply must be switched to the "RESET" 
state for approx. 5 seconds.

Meaning of the LEDs

The INSTABUS power supply is mounted on a DIN rail 
EN 50022-35. A data rail is not required. The bus con-
nection is carried out via the bus connecting terminal 
supplied with the device. The cable cover is then 
placed over the bus connecting terminal to guarantee 
the safety clearance of the bus cable to the 230 V ca-
bles. A maximum of 4 core pairs can be connected to 

Power supply 2x320 REG-K

Colour

light grey

Article no.

683729

Table of Contents

1. Function

RUN

I>I

max

RESET State

green

off

red

Slide switch in OFF or RESET 
position

green

off

off

Normal mains operation with 
I<I

max

green

red

off

Mains operation with I>I

max

the bus voltage is maintained

flashes 
green

flash-
es red

off

Mains operation with I>>I

max

the bus voltage has failed or 
there is a short circuit

off

off

off

Short circuit during mains op-
eration

2. Installation