INSTRUCTIONS 730308 Rev. -

Surge-Trap

®

 Type 1 SPD for NEMA Type 2 Applications

DANGER 

Hazard of Electric Shock, Burn or Explosion

•  This equipment must be installed and serviced only by 

qualified electrical personnel in accordance with national 

and local electrical codes.

•  Turn off all power supplying this equipment before 

working on equipment.

•  Always use a properly rated voltage-sensing device to  

confirm power is off.

•  Replace all devices, doors and covers before restoring  

power to this equipment.

•  Do not apply petroleum-based products to 

non-metallic parts.

Improper installation or misapplication of these devices 

may result in serious injury to the installer and/or damage 

to electrical system or related equipment. Protective eye 

wear and clothing should be worn whenever working 

around hazardous voltages.
Failure to follow these instructions could result in serious 

injury or death.

CAUTION

•  Do not attempt to open or tamper the Surge-Trap 

device in any way as this may compromise performance 

and will void the warranty.

•  Megger and hi-potential tests may damage the device.
•  Disconnect all power supplying the equipment and 

isolate the Surge-Trap device before testing.

•  Prior to installation, confirm that the Surge-Trap is rated 

for the correct voltage, current and frequency equivalent 

to the application.

•  For use in NEMA Type 2 Applications Only.

PANEL MOUNT AND WIRING

1.  Turn off all power supplying this equipment.
2.  Panel Mount: Remove locknut from product. Punch 

out a 1/2″ enclosure knockout from the panel or the 

mounting location as close as possible to the where the 

wires will terminate. Where other types of mounting are 

required, please consult the factory.

3.  Insert Surge-Trap® SPD wires carefully through the 

knockout hole and tighten the lock nut to 20 ft-lb 

(2.3Nm) maximum to secure the Surge-Trap® SPD to 

the enclosure. (As shown in Figure 1)

4.  Connect the wires as shown in the appropriate wiring 

diagram.

INSTALLATION

Figure 1 Panel Mount

NUT

USA   T 978 462 6662   F 978 462 0181   [email protected]
374 Merrimac Street, Newburyport, MA 01950

CANADA   T 416 252 9371   F 416 252 6572    [email protected]
88 Horner Avenue, Toronto, Ontario, Canada M8Z 5Y3

ep-us.mersen.com     

ep-ca.mersen.com

5.  Overcurrent Protection: Type 1 SPDs are UL Listed 

and tested to be self-protecting. They do not require 

upstream protection according to UL 1449 and Section 

285 of the NEC. However, we recommend an upstream 

disconnect or breaker for maintenance and safety. 

Many switches and circuit breakers have limitations 

regarding more than one wire in a connector. Breaker 

manufacturers can provide information on the limitations 

of their available terminals. Where additional wires 

are prohibited under the same terminal, many times 

installing a new circuit breaker is convenient. Typical 

sizes are 15, 20 and 30 amps.

6.  For optimal device performance, use shortest wire 

length of wire as possible. Cut off the excess wire 

instead of coiling it up. Avoid sharp bends. 

7.  Before energizing, installer shall verify service and 

separately derived system Neutral to Ground bonding 

jumper per the NEC requirements.