The STXP Series is a Type 1 SPD and suitable for use in 
all locations. Type 1 SPDs are evaluated more rigorously 
by UL for NEC

®

 Article 285 compliance. Type 1 SPDs have 

been evaluated for line side applications without need 
for supplemental overcurrent protection. Type 1 SPDs 
include internal overcurrent protection. There are practical 
maintenance reasons for installing on load side of the 
main overcurrent device (i.e. Type 2 installation). When 
connected on load side of main disconnect, its recommend 
connecting a 30A circuit breaker to protect the 10 AWG 
conductors. The circuit breaker serves as a disconnect 
switch and provides NEC

®

 imposed short circuit protection 

to the conductors in Type 2 or 4 applications. 

The STXP Series is a high quality, high energy surge 
suppressor designed to protect equipment from 
damaging transient overvoltages. The STXP Series 
is parallel connected device. Proper installation is 
important for maximize product performance. These 
installation instructions do not replace national or 
local electrical codes. 

Compliance:

The STXP Series SPD fully complies with latest UL 1449 
and NEC

®

 regulatory changes. There has been recent 

emphasis on installation location, identified as types 1, 2, 3 

or 4 locations. They are outlined below:

Type 1:

   Installation on the line side or load side of the 

service disconnect overcurrent device, and 
may be used in Type 2 or Type 4 installations. 
Examples: Surge arresters, lightning arresters, 
meter hubs, metering cabinets, ran out of breaker 
positions, etc.

Type 2:  

Downstream of service disconnect; probably will 
connect via breaker. Examples: Switchboards, 
power panels, panelboards, equipment, motors, 
pumps, etc.

Type 3:

   Plug-in SPD

Type 4:  

Usually treated as a UL Recognized component 

in a larger UL Listed finished product. Examples: 

UL 508 control panels, medical equipment, wind 
turbines, signage, conveyers, elevators, etc. 

WARNING – Risk of Electric Shock

• 

Only qualified licensed electricians should install or service 

SPDs

• 

SPDs should never be installed or serviced when energized 
or during electrical storms

• 

Use appropriate safety precautions including Personal 
Protection Equipment

• 

Failure to follow these instructions can result in death, 
serious injury, and/or equipment damage

• 

When used in outdoor applications, customer must seal 

the conduit nipple using watertight fittings (not included) to 

ensure a watertight connection

• 

Read this manual in its entirety prior to installing

NEC

®

 Art 285 & UL 1449

SPD Types: Type 1, 2, 3, & 4

Based on location within electrical distribution 

system (also coincides with ANSI/IEEE C62.41.2 - 2002 

Categories C, B &A)

Surge-Trap

®

 Type 1 

XP Series

 SPD

INSTALLATION INSTRUCTIONS