Limit Switches
Limit Switches Menu
There are two programmable limit switches, one for hopper weight and one for the Panel
Meter function.
Weight Limits
This button allows you to set the limits for the
High Weight
and
Low Weight
logical
outputs. The limits are absolute values in engineering units. When the weight exceeds
the limit the output will turn On, after the delay time.
Parameter Default
Min
Max
Unit
Hi Weight
110% of Design Weight
0%
150%
Eng
Lo Weight
-10% of Design Weight
0%
100%
Eng
Hi Wt Dly
10
0
3600
Seconds
Lo Wt Dly
10
0
3600
Seconds
The High Weight parameter is significant, because you can’t perform a Weight
Calibration procedure, if the Current Weight plus the Calibration Weight exceeds this
limit. See Weight Procedure on page 49.
Panel Meter Limits
This button allows you to set the upper and lower limits for the High Panel Mtr and Low
Panel Mtr Hi logical outputs. See Panel Meter Setup on page 31.
Parameter Default
Min
Max
Unit
Hi Output
100
0
100
%
Lo Output
0
0
100
%
Hi Outp Dly
10
0
3600
Seconds
Lo Outp Dly
10
0
3600
Seconds
35.00.EX O&M Manual
45