Communications Settings
For Baud Rate, Data Bits, Stop bits and Parity parameters, simply pushing the button for
the corresponding parameter will toggle through the available settings.
Comm 1 Numeric
For details, refer to Modbus and Scalenet documentation at
Param Meaning
Controller #
Controller Number for ScaleNet, Node Number for Modbus
Start Char
ASCII code for ScaleNet telegram start character. Default 10 (LF)
End Char
ASCII code for ScaleNet telegram end character. Default 13 (CR)
Comm Timeout
Timer for Ser Com Lost output. A value of 0 will disable the timing,
and the logical output
Ser Comm Lost
will never go on.
Com Protocol
Set to 0 for ScaleNet
Set to 1 for Modbus ASCII
Set to 2 for Modbus RTU
Write Prot
Write protection bits for Common Interface Table (CIT) variables.
Decimal representation.
Word Order
Floating point representation word order bit pattern for CIT.
Int/Frac FP
Integer Fraction floating point representation bit pattern for CIT.
Tag Reg 1 – 5
MC³ register number tagged.
Comm 2 Numeric
For details, refer to DF-1 documentation at
Param Meaning
Prtr/0 DF1/1
Set to 0 for Comm2 to be used for a serial printer
Set to 1 for Comm2 to be used for DF-1 communications
DF-1 Timeout
Timer for DF-1 Comm Lost output. A value of 0 will disable the timing,
and the logical output
DF-1 Timeout
will never go on.
DF-1 uses BCC
Set to 0 for CRC error check
Set to 1 for BCC error check.
Write Prot
Write protection bits for Common Interface Table (CIT) variables.
Decimal representation.
Word Order
Floating point representation word order bit pattern for CIT.
Int/Frac FP
Integer Fraction floating point representation bit pattern for CIT.
Tag Reg 1 – 5
MC³ register number tagged.
35.00.EX O&M Manual
44