Logical Output
Description
Cal Weights On
Place calibration weights on the feeder during a Weight
Calibration procedure. Intended for automatic calibration
equipment.
Hi Panel Mtr
An unused analog input can be used for arbitrary
measurements. This output indicates that the value has
stayed above a set limit for a set time. See Panel Meter
Setup on page 31 and Panel Meter Limits on page 45.
Low Panel Mtr
This output indicates that the panel meter value has stayed
below a set limit for a set time. See Panel Meter Setup on
page 31 and Panel Meter Limits on page 45.
Clean CMD Done
Goes on when a Cleanout sequence has completed, and the
Start Cleanout command is still on. The state will stay in
Cleanout Completed. Goes off again when the Start Cleanout
command goes off. The state will then transit to Idle.
Intended for networked PLC control.
Fdr Drive Enabl
Intended to control the feeder drive. On during Fast Feed,
Fine Feed and Cleanout. With the Manual Speed setpoint
method, the output is directly controlled from the Start/Stop
button in the Action Menu, page 17.
Vibrator
Intended to control a weigh hopper vibrator. See Vibrator
Time, page 27.
Fill Gt not Cls
The Fill gate did not closed within the
The output goes on then the time has expired, and goes off
when the
Fill Gt Closed
input goes on again.
Drive Fault
The
Drive Fault
logical input was On when
Fdr Drive Enable
logical output was On. There is a forgiveness time in R[408],
which allows for the
Drive Fault
input to stay on for a while
after
Fdr Drive Enable
turned On.
AuxIO 1-8 Delayed
These are delayed outputs available for Available IO points
1-8. Access to the time delays parameters is in the register
editor only.
On Always
Output is always ON (closed).
Off Always
Output is always OFF (open).
Available I/0 1-8
These logical I/O points are not used by any function in the
controller. Since they are both Logical Inputs and Logical
Outputs, you can use them for control purposes. If you map a
Physical Input to one of them, and then map a Physical
Output to the same point, the Output will follow the Input,
giving you one or more extra contacts, some of which can be
inverted.
List of Physical Outputs
Physical Output
Description
Rack 1 Output 1
through
8
I/O Rack 1, PCIO 1.
Rack 2 Output 1
through 8
I/O Rack 2, PCIO 1.
Rack 3 Output 1
through 8
I/O Rack 3, PCIO 2.
Rack 4 Output 1
through 8
I/O Rack 4, PCIO 2.
Extern Outpt 1
- 16
The external outputs are red by Serial
35.00.EX O&M Manual
42