8.3. Ventilation function
Ventilation function may be achieved using 2 basic methods:
by employing pneumatic actuators with appropriate installation,
by using an additional electrical actuator powered by 230V~ voltage (drawing below).
For transport reasons, the electrical actuator for ventilation function is usually not factory
installed. It is to be fixed in the upper cross-bar to the existing holes, using ST12-1/8 screws
(For Exxx-230 actuator) or threaded bolts (JMB actuators) supplied with the actuator. It is
recommended to secure the ST12 screws from loosening using Loctite 243, or similar agent.
The actuator has a T-shaped bolt that should be installed in place of the eye bolt. The hook
console should be latched onto the T bolt.
It is recommended to integrate into the system a weather automatics system for controlling
ventilation, e.g. mcrP054; its purpose is to shut any open vents in case of strong wind or
rainfall, protect user property and vent structure from damage.
Fig. 28. Ventilation control actuator
Fig.29.
‘T’ bolt
Fig. 30.
ST12-1/8 screw
(type Exxx-230)