background image

In order for the stove to perform efficiently and safely there should be an adequate air supply into the room in which the
stove is installed to provide combustion air.  This is particularly necessary if the room is double-glazed or a flue draught
stabiliser is operating in the same room as the appliance. The provision of air supply to the stove must be in accordance with
current Building Regulations Approved Document J. An opening window is not appropriate for this purpose. Air inlets must
be positioned in such a way that they cannot be blocked. An air inlet may be a vent (the vent must be open and the capacity
for the vent sufficient when the stove is lit) .

There are no European rules regarding the minimum distance to non-flammable walls, Mendip Stoves recommend leaving

a gap of at least 100mm behind and to sides of stove.

The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not independently

supported. Churchill, Loxton and Sqabox stoves have been tested and are suitable to be installed on a 12 mm non combustible
plate such as  12 mm glass plates . Installation of all hearths should comply in size and construction so that it is in accordance
with the provisions of the current Building Regulations Approved Document J.

The clearance distances to combustible material beneath, surrounding or on the hearth and walls adjacent to the hearth

should comply with the guidance on the separation of combustible material given in Building Regulations Approved Document
J and also in these stove instructions.
If the stove is to be installed on a wooden floor, it must be covered with a non-combustible material at least 12 mm thick,
in accordance with Building Regulations Approved Document J, to a distance of 30 cm in front of the stove and 15 cm to
each side measuring from the door of the combustion chamber.

HEARTH

COMBUSTION AIR

COMBUSTION CHAMBERS

Mendip Stoves are  fitted internally with vermiculite heat deflection panels and baffles, these panels are designed to ensure
the maximum efficiency and are an integral part of the clean burn process of the stove. These baffles should not be removed
other than for cleaning the stove. Any defective panels should be replaced, small hairline cracks do need replacement and
can develop during long term use.  When refuelling  your stove place wood fuel into the chamber,  impact from logs can
cause  the heat deflection panel to crack

.

Connection to chimney

Mendip Stoves are built with a top flue outlet as standard, this can be altered to a rear connection by removing  the top
collar, rear cover plate then exchanging collar and plate. Care should be taken to ensure an airtight fit when refitting collar
and plate. A decorative cover plate is included in each stove to cover the hole in the convection top plate. This collar
allows connection to either a masonry chimney or a prefabricated factory made insulated metal chimney.

COMMISSIONING AND HANDOVER

Ensure loose parts  ( brick and grates) are fitted in accordance with the instructions  given in the instruction booklet. On
completion of the installation allow a suitable period of time for any fire cement and mortar to dry out, a small fire may be
lit to check that smoke and fumes are taken from the stove up the chimney and emitted safely into the atmosphere. Do not
run at full output for at least 24 hours.

On completion of the installation and commissioning ensure that the operating instructions for the stove are left with the

customer. Ensure to advise the customer on the correct use of the appliance with the fuels likely to be used in the stove and
notify them to use only the recommended fuels for the stove. Advise the user what to do should smoke or fumes be emitted
from the stove.

The customer should be warned to use a fireguard to BS 8423:2002 in the presence of children, aged and/or infirm persons.

Summary of Contents for Burcott Multi-fuel

Page 1: ...Burcott Fireplace inset stove ENG FR OPERATION AND INSTALLATION MANUAL Multi fuel and SE models Guide d utilisation et Mode d Emploi...

Page 2: ...blems Please note that all local regulations including those referring to national and European Standards need to be complied with when installing this appliance For further information on installing...

Page 3: ...fitted in the same room as the appliance Further guidance on the installation of the carbon monoxide alarm is available in BS EN 50292 2002 and from the alarm manufacturer s instructions Provision of...

Page 4: ...actory Alternatively the calculation procedure given in BS5854 1980 may be used as the basis for deciding whether a particular chimney design will provide sufficient draught If it is found that there...

Page 5: ...liance from the opening 2e Using a masonry bit drill corresponding holes in the hearth and fit 1 x 6mm floor bolt 2f The appliance is now ready to be secured to the hearth afterthe flue system has bee...

Page 6: ...ppliances can be affected by temporary atmospheric conditions which may allow fumes to enter the house Building regulations require that whenever a new or replacement fixed solid fuel or wood biomass...

Page 7: ...STOVE DIMENSIONS AND CONNECTION MEASUREMENTS...

Page 8: ...x 7cm x 6 cm Output wood fuel Efficiency CO 13 o2 Recommended for smoke control Oct 2014 Output coal fuel Efficiency CO 13 o2 Burcott 4 1kw 83 0 38 YES 3 9kw 79 0 36 Mendip Stoves Burcott models are...

Page 9: ...oor of the combustion chamber HEARTH COMBUSTION AIR COMBUSTION CHAMBERS Mendip Stoves are fitted internally with vermiculite heat deflection panels and baffles these panels are designed to ensure the...

Page 10: ...TIME Before lighting your stove for first time make sure you have read this manual fully and acquainted yourself with the controls of this appliance see page 9 The heat resistant paint on your stove w...

Page 11: ...t closed To Open door lift handle To close push door closed and push handle down until located When opening the door of your Mendip stove always wear the glove that is provided to protect your hand fr...

Page 12: ...e the primary slider again 6 Once established close the secondary air slider by 50 for the stove to burn cleanly plenty of secondary air is needed do not be tempted to shut the fire down too early as...

Page 13: ...ld not be attempted Mendip smoke control stoves should not be burnt with the door left open The refuelling procedure allow the newly charged fuel to burn with the secondary air control set at maximum...

Page 14: ...ed when operating air controls and door Re fueling solid fuel To re fuel your stove Before refuelling open Primary and secondary air controls to fully open Open door gently and de ash your stove with...

Page 15: ...cleanly if it is burnt hotter Mendip stoves do not recommend that their stoves are burnt overnight for this reason As a night time regime we recommend that the fire is loaded when hot and burnt for fi...

Page 16: ...there is an adequate air supply into the room e that an extractor fan is not fitted in the same room as the fire 2 Fire Blazing Out Of Control check a the doors are tightly closed b the air controls a...

Page 17: ...le po le est en cours d utilisation Votre po le comprend les l ments suivants dans le po le This section shows the parts contained in your stove each stove has over 80 spare parts and each part is det...

Page 18: ...Baffle plate and remove left front brick Then remove steel baffle plate This will leave the flue free for cleaning Fig 5 Slide rear brick to the left and remove Fig 3 Fig 4 Fig 1 Fig 2 Fig 5 Fig 1 Bur...

Page 19: ...with the front right brick the front brick has a routed out section for the handle mount to fit see fig 9 Place the bricks back in the chamber as they where taken out Ensure the baffle is put back in...

Page 20: ...Somerset BS26 2UG Tel 01934 750 500 Fax 01173 156 207 www Mendipstoves co uk E mail info mendipstoves co uk Distribu en France par la soci t Distributed in France and Benelux by Eurostove SAS Centre...

Reviews: