User guide
Wireless remote control M-WRG-FBH
- 37 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
Code Parameter
Min. Max. Incre-
ment
De-
fault
Unit
Comment
154
(6)
Delay time with
2 sensors
0
120
1
10
min
168
(1)
External switch I
mode
0
18
1
0
169
(1)
External switch II
mode
0
18
1
1
170
(1)
External switch III
mode
0
18
1
2
93
Restore factory
default settings
0
1
1
0
1 = restore factory default
settings
Table 7: Variable parameters in the Device settings menu for ventilation units from the M-WRG-II series
(1) See list of modes in section 9.4.5 on page 40
(2) Hold down the
or
button to scroll through the values faster
(3) For the M-WRG-II P-T-F / M-WRG-II E-T-F and M-WRG-II P-T-FC / M-WRG-II E-T-FC unit types, the wireless remote
control can be used to assign the “CO
2
” program button on the InControl pushbutton sensor to the “Automatic mode”
ventilation program. In this case, the ventilation mode will be regulated in relation to the CO
2
concentration
and
the
relative room air humidity.
(4) Code 101 is used to set up buttons 1 to 3 on the 4-way wireless pushbutton switch M-WRG-FT and for the wireless
sensors:
Value 1: button 1, 2, 3 = LOW, MEDIUM, HIGH
Value 2: ventilation programs activated for codes 168 to 170
(5) Only needed for the InControl pushbutton sensor
(6) Only needed for the M-WRG-II O/VOC-AUL option
9.4.4 Variable parameters for ventilation units from the M-WRG series
Code Parameter
Min. Max. Incre-
ment
De-
fault
Unit
Comment
84
Fan motors oper-
ating hours
Running time of the fan
motors
83
Ventilation unit
operating hours
Unit switched on (also
applies to standby mode)
13
Air flow in
LOW mode
0
100
10
10
m
3
/h
LOW = reduced ventilation
14
Air flow in
MEDIUM mode
0
100
10
30
m
3
/h
MEDIUM = normal ventila-
tion
15
Air flow in
HIGH mode
0
100
10
60
m
3
/h
HIGH = increased ventila-
tion
44
This code only applies for ventilation units from the M-WRG-II series
45
This code only applies for ventilation units from the M-WRG-II series
11
Air flow for inten
-
sive ventilation
0
100
10
100
m
3
/h
12
Intensive ventila-
tion duration
0
240
1
15
min