User guide
Wireless remote control M-WRG-FBH
- 26 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
8.2.5 “Automatic mode”
Symbol
Default view
Description
This ventilation program combines the “Humidity control” (see
section 8.2.3 on page 25, ) and “Mixed gas/CO
2
control” (see
section 8.2.4 on page 25) ventilation programs. In automatic
mode, the relative room air humidity is monitored in addition to
the mixed gas/CO
2
concentration. The mixed gas/CO
2
sensor
and the humidity sensor each send feedback to the ventilation
unit, indicating the ventilation level at which it should work. The
ventilation unit automatically assumes the higher of the two
suggested ventilation levels and thus ensures the priority.
NOTICE
►
Note the information on calibrating the mixed gas/CO
2
sensor in section 8.2.4 on page 25.
8.2.6 “Continuous operation”
Symbol
Default view
Description
The ventilation unit runs in continuous operation. By default,
ventilation level 3 (30 m
3
/h) is set for supply air and extract air.
8.2.7 “Intensive ventilation (15 min)”
Symbol
Default view
Description
The ventilation unit runs at maximum ventilation level
(100 m
3
/h). After 15 minutes (factory default setting), the previ-
ously set ventilation program is resumed.
Hold down the
button for more than 3 seconds to activate
or deactivate intensive ventilation.
Press the
or
button to adjust the ventilation level
temporarily while intensive ventilation is running. The default
setting will be resumed when intensive ventilation is used
again.
8.2.8 Device settings
Symbol
Default view
Description
–
This menu is used to read, configure and permanently store the
ventilation program parameters and device-specific settings.