User guide
Wireless remote control M-WRG-FBH
- 39 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
Code Parameter
Min. Max. Incre-
ment
De-
fault
Unit
Comment
119
This code only applies for ventilation units from the M-WRG-II series
120
This code only applies for ventilation units from the M-WRG-II series
7
Pause time
1
255
1
60
min
Time interval for which the
ventilation unit pauses in
sniffing mode.
8
Sniffing time
5
255
1
5
min
Time interval for which
recording of the relative
atmospheric humidity and
the mixed gas/CO
2
concen-
tration takes place
9
Air flow in sniffing
mode
10
100
10
20
m
3
/h
Air flow during the recording
of the relative atmospheric
humidity and the mixed gas/
CO
2
concentration
10
Position of air
flaps in Standby
mode
0
1
1
1
-
0: air flaps open in Standby
mode
1: air flaps closed in
Standby mode
42
Air flow for extract
air in supply air
operation ventila-
tion program
0
100
10
15
m
3
/h
InControl pushbutton sensor
and M-WRG-FBH wireless
remote control
43
Air flow for supply
air in supply air
operation ventila-
tion program
0
100
10
50
m
3
/h
InControl pushbutton sensor
and M-WRG-FBH wireless
remote control
46
Air flow for extract
air in extract air
operation ventila-
tion program
0
100
10
50
m
3
/h
InControl pushbutton sensor
and M-WRG-FBH wireless
remote control
47
Air flow for supply
air in extract air
operation ventila-
tion program
0
100
10
15
m
3
/h
InControl pushbutton sensor
and M-WRG-FBH wireless
remote control
196
This code only applies for ventilation units from the M-WRG-II series
57
Ventilation level
for continuous
operation
0
100
10
30
m
3
/h
Ventilation levels for supply
air and extract air are set at
the same time
50
(3)
InControl push-
button sensor:
mixed gas/CO
2
control or auto-
matic mode
0
1
1
0
-
0: mixed gas/CO
2
control
1: automatic mode