![Melink Intelli-Hood IH3 SC Manual Download Page 5](http://html1.mh-extra.com/html/melink/intelli-hood-ih3-sc/intelli-hood-ih3-sc_manual_1767441005.webp)
Page | 4
Object/Property Support Matrix
The following table summarizes the Object Types/Properties Supported:
Object Type
Analog Range or
Binary
Active/Inactive Text
Present
Value Access
Type
Object
Number
Object Name
(Value Text)
Binary
Value
Analog
Value
System Controller
Digital Input 1 Status
Closed/Open
Read only
BV0
Digital Input 2 Status
Closed/Open
Read only
BV1
Digital Input 3 Status
Closed/Open
Read only
BV2
Digital Output 1 Status
Energized/De-
Energized
Read only
BV3
Digital Output 2 Status
Energized/De-
Energized
Read only
BV4
24VDC Out 1 Status
Energized/De-
Energized
Read only
BV5
24VDC Out 2 Status
Energized/De-
Energized
Read only
BV6
Analog Input Status
0-100%
Read only
AV0
Analog Output Status
0-100%
Read only
AV1
For each Exhaust Fan and
Auxiliary Airflow
Operation Status
Running/Stopped
Read only
BV0
Fault Active
Yes/No
Read only
BV1
Reset VFD Fault
Yes/No
Commandabl
e
BV2
Maximum Output
Frequency
0-254 Hz
Read only
AV0
% Commanded Speed
0-100%
Read only
AV1
% Actual Speed
0-100%
Read only
AV2
Output Current
1
0-32768 A
Read Only
AV3
Output Energy
2
0-32768 kWh
Read Only
AV4
1
Output Current is not updated for System and Trane TR-200 VFDs
2