MA-5195-ENG
PS20 NON STOP+ DRUM UNLOADER MANUAL
MELTER OPERATION
4-37
Standby function
Using the standby function during periods of melter/applicator inactivity helps
save energy and allows the heated elements to return quickly to their set point
temperatures once you return to the operational mode.
When the function is activated, the target temperature of the heated zones is
reduced to the programmed value for each zone (see ‘Heating menu / Heating
zones’).
For example, if the target temperature of the tank is 160°C and the Under
Maintenance parameter is set to -30ºC, when the Under Maintenance function
key is pressed, the tank’s set point temperature will change to 130ºC.
The priority protocol is as follows:
1st Under Maintenance external signal.
2nd ‘Under Maintenance’ function key.
or calendar programming.
3th individual Under Maintenance function key.
Therefore, while the Under Maintenance external signal remains active,
none of the other three systems can deactivate the function.
The following criteria are suggested for standby function use:
- If the period of inactivity is less than 2 hours, allow the melter
applicator equipment to heat as normal.
- If the period of inactivity is more than 2 hours and less than 4 hours,
use the standby function.
- If the period of inactivity is over 4 hours, use one of the following two
options: turn off the equipment if you do not plan on using it for the
rest of the day or keep the standby function on if you plan on using the
equipment during that same day.
HMI
: S02001100 v1.0.106
TC
: S02200100 v1.0.084
IO
: S02102100 v1.0.106
IO
: S02101100 v1.0.106
Group OFF
OFF Group: 1
Temperature
State
Area
Standby
OFF
1.1: Hose 1
1.2: Applicator 1
2.1: Hose 2
2.2: Applicator 2
3.1: Hose 3
3.2: Applicator 3
General Standby
General OFF
1
HMI
: S02001100 v1.0.106
TC
: S02200100 v1.0.084
IO
: S02102100 v1.0.106
IO
: S02101100 v1.0.106
Group OFF
OFF Group: 1
Temperature
State
Area
Standby
OFF
1.1: Hose 1
1.2: Applicator 1
2.1: Hose 2
2.2: Applicator 2
3.1: Hose 3
3.2: Applicator 3
General Standby
General OFF
2
HMI
: S02001100 v1.0.106
TC
: S02200100 v1.0.084
IO
: S02102100 v1.0.106
IO
: S02101100 v1.0.106
DI1
DI2
DI3
DO2
DO3
DO4
2.3 Input / Output
Imput
Output
Standby
COMs OFF
Pump OFF
Level
Machine ready
Alarm
2
HMI
: S02001100 v1.0.106
TC
: S02200100 v1.0.084
IO
: S02102100 v1.0.106
IO
: S02101100 v1.0.106
C1 C2 C3 C4 C5 C6
Calendar
Hour
ON
Standby
OFF
07:00
11:00
13:15
15:00
00.00
00.00
Enable all the calendars
M
T
W
T
F
S
S
2
Summary of Contents for PS 20 NON STOP+
Page 1: ...GLUING SOLUTIONS MA 5195 ENG 010620 ADHESIVE MELTER PS20 NON STOP INSTRUCTIONS MANUAL ...
Page 8: ...FOCKE MELER GLUING SOLUTIONS TABLE OF CONTENTS This page is intentionally left blank ...
Page 68: ...FOCKE MELER GLUING SOLUTIONS 4 42 MELTER OPERATION This page is intentionally left blank ...
Page 80: ...FOCKE MELER GLUING SOLUTIONS 6 2 TECHNICAL CHARACTERISTICS Dimensions ...
Page 81: ...ELECTRICAL DRAWINGS 7 1 MA 5195 ENG PS20 NON STOP DRUM UNLOADER MANUAL 7 ELECTRICAL DRAWINGS ...
Page 82: ...FOCKE MELER GLUING SOLUTIONS 7 2 ELECTRICAL DRAWINGS This page is intentionally left blank ...
Page 84: ...FOCKE MELER GLUING SOLUTIONS 8 2 PNEUMATIC DRAWING 16 17 19 18 10 11 12 13 14 15 ...
Page 86: ...FOCKE MELER GLUING SOLUTIONS 8 4 PNEUMATIC DRAWING This page is intentionally left blank ...
Page 88: ...FOCKE MELER GLUING SOLUTIONS 9 2 SPARE PARTS LIST This page is intentionally left blank ...