Page 1: ...MANUAL GNSS MULTI BAND Antenna Antenna Converter Unit 25th February 2020 Meinberg Funkuhren GmbH Co KG ...

Page 2: ......

Page 3: ...ng Materials 4 4 Installation GNSS Multiband Antenna 5 5 Technical Specifications GNSS Multiband Antenna 9 5 1 MBG S PRO Technical Specifications 11 5 1 1 MBG S PRO Physical Dimensions 13 5 1 2 Installation and Grounding 13 6 RoHS and WEEE 14 7 EU Declaration of Conformity 15 Date 25th February 2020 GNSS MULTI BAND Antenna ...

Page 4: ...nkuhren GmbH Co KG Lange Wand 9 31812 Bad Pyrmont Germany Phone 49 0 52 81 93 09 0 Fax 49 0 52 81 93 09 230 Internet https www meinbergglobal com Mail info meinberg de Date 2020 02 25 GNSS MULTI BAND Antenna Date 25th February 2020 1 ...

Page 5: ...a proper fall protection device Do not carry out any installation or maintenance work on the antenna system or cabling when there is a potential risk of lightning Surge Voltage Protector Due to extremely high currents associated with lightning no surge protection device can provide absolute safety from the impacts caused by lightning 2 Date 25th February 2020 GNSS MULTI BAND Antenna ...

Page 6: ...ack the system and all accessories and put them aside Check the scope of delivery with the pack ing list to ensure that no parts are missing If any of the listed contents are missing please contact Meinberg Funkuhren Check the system for shipping damage If the system is damaged or cannot be put into operation contact Meinberg Funkuhren immediately Only the recipient the person or company receiving...

Page 7: ...l Use for Disposal Polystyrol packaging frame filling material Recycling Depot polystyrene peanuts bubble wrap PE LD accessories packaging Recycling Depot Polyethylene low density Cardboard shipping packaging Paper recycling accessories packaging 4 Date 25th February 2020 GNSS MULTI BAND Antenna ...

Page 8: ...ed 1 Selection of the Antenna location To receive enough satellites select a location that allows an unobstructed view of the sky otherwise there may be problems with the synchronization of the system There should be no obstacle in the line of sight between the antenna and the satellites In addition the antenna must not be installed under high voltage lines or other electrical light or electric ci...

Page 9: ...tenna cable Belden H155 to the N Norm connector of the antenna Lead the other end of the cable through the wall into the building GNSS Antenna N Norm female N Norm male Free view to the sky Make sure that the maximum cable length is kept when installing the antenna cable between the antenna and receiver This depends on the type of cable used H155 RG58 and its damping factor 6 Date 25th February 20...

Page 10: ...ide of the antenna cable to the surge protection socket N Norm male N Norm female Outside wall of the building Outdoor installation Inside a waterproof housing Indoor installation recommended Just after the antenna cable enters N Norm female N Norm male M B G S P R O M B G S P R O the wall 3 The next step is to connect the supplied coaxial cable between the surge protector and receiver N Norm fema...

Page 11: ...signal is delayed by the used coaxial cable The connected receiver must compen sate the signal propagation time of the antenna cable therefore you need to enter the length of the antenna cable in meters or the compensation time in nanoseconds into the settings of your receiver Antenna Cable Length m Cable Delay Usage RG58U 5 ns m for GPS180 and GNS UC H155 4 ns m for GNS180 and GNM By entering the...

Page 12: ...5 Technical Specifications GNSS Multiband Antenna 5 Technical Specifications GNSS Multiband Antenna Physical Dimensions GNSS MULTI BAND Antenna Date 25th February 2020 9 ...

Page 13: ...L1 L2 L5 GLONASS G1 G2 G3 Beidou B1 B2 Galileo E1 E5a b plus L band Out of band rejection Freq Band L5 E5 L2 G2 Frequency Gain 1050 MHz 45 dB 1125 MHz 30 dB 1350 MHz 45 dB Freq Band L1 E1 B1 G1 Frequency Gain 1450 MHz 30 dB 1690 MHz 30 dB 1730 MHz 40 dB Connector N Norm female Form factor ABS plastic case for outdoor installation Protection class IP66 Humidity 95 Temperature range 40 C to 85 C 40 ...

Page 14: ... is equipped with two type N female connectors It has no dedicated input output polarity or prefered mounting orientation Phoenix CN UB 280DC BB Features High RF Performance Multiple Strike Capability 20 kA Surge Protection Bi directional Protection Mounting type Connection specific intermediate plugging Type Attachment plug Direction of action Line Shield Earth Ground Maximum continuous operating...

Page 15: ...2 GHz Permissible HF power Pmax at VSWR xx 50 ohm system 700 W VSWR 1 1 200 W VSWR Capacity Core Earth typ 1 5 pF asymmetrical shield typ 1 5 pF Surge current resistance conductor ground C1 1 kV 500 A C2 10 kV 5 kA C3 100 A D1 2 5 kA Ambient temperature operation 40 C 80 C Altitude 2000 m above sea level Degree of protection IP55 Housing material Nickel plated brass Color nickel Dimensions Height ...

Page 16: ...5 Technical Specifications GNSS Multiband Antenna 5 1 1 MBG S PRO Physical Dimensions 67 11 15 8 25 13 4 5 1 2 Installation and Grounding GNSS MULTI BAND Antenna Date 25th February 2020 13 ...

Page 17: ...biphenyls PBBs and polybrominated diphenyl ethers PBDEs Bis 2 ethylhexyl phthalat DEHP Benzylbutylphthalat BBP Dibutylphthalat DBP Diisobutylphthalat DIBP above the legal threshold WEEE status of the product This product is handled as a B2B Business to Busi ness category product In order to secure a WEEE compliant waste disposal it has to be returned to the manufacturer Any transportation expenses...

Page 18: ...which this declaration relates is in conformity with the following standards and provisions of the directives RED Richtlinie ETSI EN 303 413 V1 1 1 2017 06 RED Directive 2014 53 EU EMV Richtlinie Draft ETSI EN 301 489 1 V2 2 0 2011 09 EMC Directive Draft ETSI EN 301 489 19 V2 1 0 2011 09 DIN EN 61000 6 2 2005 2014 30 EU DIN EN 61000 6 3 2007 A1 2011 DIN EN 55032 2015 DIN EN 55024 2010 Niederspannu...