MTC-04-NTT Thermostat User Manual

Thank you for using Megmeet MTC-04-NTT module. Before using the

PLC product, please carefully read this booklet so as to better

understand it, fully use it, and ensure safety.This user manual is to offer

you a quick guide to the design, installation, connection and

maintenance of MTC-04-NTT module, convenient for on-site reference.

Briefly introduced in this booklet are the hardware specs, features, and

usage of MTC-04-NTT

modu

le, plus the optional parts and FAQ for

your reference.

This manual MTC-04-NTT module for the following members:

MTC-04-NTT Thermostat User Manual

Version

1.0

Revision date

July 16, 2012

BOM

1.Introduction

Model description as 1-1.

Output Method

R: Relay Output

T: Transistor Output

Input method

N: No CT (Current test)

Input

The same input and

output

channels

of

channel number and

module number

Thermostat

Megmeet

TT

M TC 04

-

-

N

Table 1-1 Module Description

2.Wiring Instructions

User input wiring terminals shown in figure 2-1.

Table 2-1 MTC-04-NTT enter the user terminal wiring diagram

Figure

~

wiring must be noted that seven aspects:

The thermocouple (thermal resistance) signal is recommended to be

accessed via a shielded cable (connection cable). Cables should be

kept away from power lines or other wires that may cause

electromagnetic interference. It is recommended to use cables less

than 100 meters in length (connecting cables). There is impedance in

the cable (connecting cable), which will introduce measurement error.

Characteristic adjustment can solve this problem. For specific operation,

please refer to "

MTC-04-NTT

thermostat user manual".

Thermal resistance (type Pt100, JPt100, Cu100, Cu50)

required the three-wire connection.

If there is too much electrical interference, the shield wire

(thermocouple compensationcable shielding terminal, thermal

resistance of the connecting cable shielding terminal 485 linescreen)

should be connected to ground terminal PG.

The thermostat grounding PG should be good grounding.

24V power supply can use the main output of 24Vdc auxiliary power

supply module, you can also use the other to meet the

requirements of power.

3.2 user basis having the output performance indicators to select

the appropriate power supply and solid state relays

4 external input support source input and sink input, input voltage

range DC18V ~ DC28V.

3.Instructions

3.1 Power indicator

The power indicator of MTC-04-NTT is shown in figure 3-1.

Table 3-1 Power indicator

Project

Instruction

Power

24Vdc (-15%

20%), the maximum allowable ripple

voltage 5%, maximum power consumption 160mA.

3.2 Performance indicators

Table 3-2 Performance indicators

Project

Indicators

Input signal

Thermocouple

type

K

J

E

N

T

R

S

B

Applicable

to each channel

Thermal

resistant type

Pt100

Cu100

JPt100

Cu50

Ni120

Applicable to each channel

Output

method

The output

gate open

transistor

Power supply voltage circuit

5V

24V

The biggest power supply voltage

circuit

30V

Loop current

0.3A/24Vdc

leakage current when open

:<

0.1mA/30Vdc

Minimum load

5mA

5Vdc

24Vdc

Delay output

DC30V or

AC250V; Current

2A

Input port Input method

Support source input and sink input

Voltage range DC18V~DC28V

Sampling period

100 milliseconds or 1 second (optional)

Control cycle

0.1~2seconds or 1

100 seconds

The

default value for 0.2s or 2s

Control method

ON/OFF control

Hand control

PID

control.Heating and cooling PID

control

Nominal

Temperat

ure Rang

e

Type K

100

1200

(-

148

2192

Type J

100

600

(-

148

1112

Type E

100

850

(-

148

1562

Type N

100

1200

(-

148

2192

Type T

200

300

(-

328

572

Type R

0

1600

32

2912

Type S

0

1600

32

2912

Type B

400

1800

752

3272

Pt100

150

600

(-

238

1112

JPt100

150

500

(-

238

932

Cu100

30

120

(-

22

248

Cu50

30

120

(-

22

248

Ni120

80.0

280.0

(-

112.0

536.0