1
MC200-5AM Analog I/O Module
User Manual
To reduce the chance of accident, please carefully read the operation
instructions and notes in this book prior to use. Only adequately trained
personnel shall install or operate this product. Strict compliance with the
safety rules in relevant industries, the operation instructions and safety
precautions provided in this book is required in equipment operation.
1 Port Description
1.1 Port
The extension port and user port of MC200-5AM are both protected by a
cover, as shown in Figure 1-1. Removing the covers reveals the extension
port and user port, as shown in Figure 1-2.
P
O
W
ER
24
V
R
UN
EC
20
-5
AM
Extension cable
Extension port cover
User port cover
26
2
25
P
O
W
E
R
24
V
R
UN
EC
20
-5 AM
10
2
4
6
8
20
12 14
16 18
9
1
3
5
7
19
11
13 15 17
V2+
24V-
V1+
I1+
24V+ FG
VI2-
I2+ I3+
VI3-
V4+ I4+ VO+ IO+
User port
Extension port
Extension cable
VI1-
V3+
VI4-
VIO-
Figure 1-1 MC200-5AM appearance
Figure 1-2 Module ports
The extension cable connects MC200-5AM to the system, while the
extension port connects MC200-5AM to another extension module of the
system. For details on connection, See
1.2 Connecting Into System.
The user port of MC200-5AM is described in Table 1-1.
Table 1-1 MC200-5AM user port description
Terminal Name
Description
Terminal Name Description
1
24V+
Analog power supply
24V+
11
V3+ CH3 voltage input
2
24V-
Analog power supply
24V-
12
I3+ CH3 current input
3
FG Shielding ground
13
VI3- CH3 common GND
4
PG Protection ground
14
V4+ CH4 voltage input
5
V1+ CH 1 voltage input
15
VI4- CH4 common GND
6
I1+ CH 1 current input
16
I4+ CH4 current input
7
VI1- CH1 commond GND
17
·
NC
8
V2+ CH2 voltage input
18
VO+ Voltage output
9
VI2- CH2 commnd GND
19
VIO-
Output channel
common GND
10
I2+ CH2 current input
20
IO+ Current output
Note:
An input channel cannot receive both voltage signals and current
signals at the same time. If you intend to use a channel for current
measurement, short its voltage input terminal and current input terminal.
1.2 Connecting Into System
Through the extension cable, you can connect MC200-5AM to MC200 series
basic module or other extension modules. While through the extension port,
you can connect other MC200 series extension modules to MC200-5AM. See
Figure 1-3.
Basic module
Extension module
Removing extension port cover
before connection
Extension cable
Figure 1-3 Connecting into system
1.3 Wiring
Figure 1-4 shows the wiring of the user port.
I1+
CH1
24 V+
24 V-
DC /DC
converter
AGND
+
5V
-
5 V
PG
N
D
EC
20
-
5AM
24
V
dc
±
10
%
60
m
A
V1+
VI 1-
FG
AGND
250
130
K
130
K
390
K
390
K
AGND
Current input
I4+
CH4
V4+
VI 4-
FG
AGND
250
130
K
130
K
390
K
390
K
AGND
Voltage input
①
②
②
③
①
Load
CHO
IO+
VO+
VIO -
AGND
①
②
④
⑤
⑨
⑥
⑦
⑧
Figure 1-4 Wiring of MC200-5AM user port
The circled 1 ~ 9 stands for the nine points to be observed during wiring.
1. It is recommended to use shielded twisted pair for the analog input and
output and separate them from power cables and any cable that may
generate EMI.
2. If the I/O signal has electric noise or voltage fluctuation, it is advisable to
connect a smoothing capacitor (0.1µF ~ 0.47µF/25V).
3. If strong EMI exists, connect the FG terminal to the PG terminal.
4. Each load of the PLC should be grounded separately
.
5. If a channel is used for current input, short its voltage input terminal and
current input terminal.
6. Shorting the voltage output terminals or connecting current load to voltage
output terminals may damage MC200-5AM.
7. Properly ground the module’s PG terminal.
8. The basic module’s 24Vdc auxiliary power or other qualified external
power supply can be used as the power source of the module’s analog
circuit.
9. Do not use the NC terminal.
2 Indices
2.1 Power Supply
Table 2-1 Power supply
Item
Description
Analog circuit
24Vdc (-15%~20%), maximum allowable ripple voltage
5%, 90mA (from basic module or external power supply)
Digital circuit
5Vdc, 50mA (from basic module)
2.2 Performance
Table 2-2 Performance
Item
Index
Conversion
speed
AD conversion
15ms/channel (normal)
8ms/channel (high speed)
DA conversion 6ms/channel (max.)
Analog
input
Voltage
-10 ~ 10Vdc (input impedance 200kΩ)
Warning: this module may be damaged if
the input voltage exceeds ±15Vdc
Current
-20~20mA (input impedance 250Ω)
Warning: this module may be damaged if
the input current exceeds ±32mA
Analog
output
Voltage
-10~10Vdc (external load impedance ≥ 2kΩ)
Current
0~20mA (external load impedance ≤ 520Ω)
Digital output
Default: -2000 ~ 2000
Setting range: -10000 ~ 10000
Digital input
Default: -2000 ~ 2000
Setting range: -10000 ~ 10000
Resolution
Voltage input
5mV
Current input
10µA
Voltage output 5mV
Current output 10µA
Accuracy
Analog input
±1% of full range
Analog output ±1% of full range