13

4 SETuP AND OPERATION 

tions" on page 12 are complete, the mains 
power cord is connected to the power outlet.

5] 

Set the "RANGE"selector to the required 
test current, as high as possible but not more 
than 10% of rated current (power transform-
ers, reactors, rotating machines). For a CT, 
preferably use 1 A.

6] 

For Single winding 

Set switch "R2 SENSE" to "OFF" position. 

For Dual windings: 

Set switch "R2 SENSE" to "ON" position. 

7] 

Set switch "TEST CURRENT" to "ON", to initi-
ate current. 

8] 

The current and resistance values must be 
observed on the display. Wait for the stabil-
ity reading to reach 100% and then note the 
displayed resistance value in the supplied 
reporting sheet or other location.

9] 

When the measurement is finished set the 
"TEST CURRENT" switch to "OFF".  
The "DISCHARGE" lamp and sound will indi-
cate that the discharging is in progress. 

10] 

Discharge is complete when both discharge 
indicator and "TEST CURRENT" lamp are off.

 Warning 

Do not disconnect any test leads until 
the "DISCHARGE" light goes out and the 
sound stops.

Note

  The discharge of a transformer after testing is 

critical to prevent excessive voltage build-up 
across the transformer bushings upon removal 
the test leads. The MTO106 discharge circuitry 
is built-in and will automatically initiate when 
the current source is disconnected from the 
transformer. It will also provide visual and 
audible indication of discharging. 

4.3 Testing Delta winding 
resistance

Testing Delta winding resistance may be a very time 
consuming procedure, in particular LV winding 
deltas. The correct balance time can take up to 30-60 
minutes for a large transformer, which far exceeds the 
time restriction of many tests. 
The method for quickly testing delta configurations 
requires that both the high side and low side be 
connected in series with the Transformer Ohmmeter’s 
current source (see connection table 1). By using 
both HV and LV windings to magnetize the core, the 
effective test current increases with the turn ratio.

Table 1. Transformer connection schemes for 
injecting test current and measuring two 
windings

Vector 
Group

Measurement setup

Current Connections

Meas 

ch 1

Meas 

ch 2

+ Current

Jumper

- Current

+

-

+

-

Dd0

H1

H3-X1

X3

H1

H3

X1

X3

H2

H1-X2

X1

H2

H1

X2

X1

H3

H2-X3

X2

H3

H2

X3

X2

Dyn7

H1

H3-X0

X1

H1

H3

X0

X1

H2

H1-X0

X2

H2

H1

X0

X2

H3

H2-X0

X3

H3

H2

X0

X3

Dyn1

H1

H3-X1

X0

H1

H3

X1

X0

H2

H1-X2

X0

H2

H1

X2

X0

H3

H2-X3

X0

H3

H2

X3

X0

YNyn0

H1

H0-X1

X0

H1

H0

X1

X0

H2

H0-X2

X0

H2

H0

X2

X0

H3

H0-X3

X0

H3

H0

X3

X0

Ynd1

H1

H0-X1

X2

H1

H0

X1

X2

H2

H0-X2

X3

H2

H0

X2

X3

H3

H0-X3

X1

H3

H0

X3

X1

Dy1

H1

H3-X1

X2

H1

H3

X3

X2

H2

H1-X2

X3

H2

H1

X1

X3

H3

H2-X3

X1

H3

H2

X2

X1

YNd7

H1

H0-X2

X1

H1

H0

X2

X1

H2

H0-X3

X2

H2

H0

X3

X2

H3

H0-X1

X3

H3

H0

X1

X3

Dyn5

H1

H2-X0

X1

H1

H2

X0

X1

H2

H3-X0

X2

H2

H3

X0

X2

H3

H1-X0

X3

H3

H1

X0

X3

Dy11

H1

H3-X1

X3

H1

H3

X1

X3

H2

H1-X2

X1

H2

H1

X2

X1

H3

H2-X3

X2

H3

H2

X3

X2

Dyn11

H1

H2-X1

X0

H1

H2

X1

X0

H2

H3-X2

X0

H2

H3

X2

X0

H3

H1-X3

X0

H3

H1

X3

X0

Summary of Contents for MTO106

Page 1: ...WWW MEGGER COM User s Manual Art No ZP BN01E Doc BN034794AE V01a 2018 MTO106 Transformer ohmmeter...

Page 2: ......

Page 3: ...iptions or software listings that disclose source code are for informational purposes only Reproduction in whole or in part to create working hardware or software for other than Megger Sweden AB produ...

Page 4: ...enance 9 3 Instrument description and Accessories 10 3 1 Panel 10 3 2 The display 11 3 3 Accessories 11 Included 11 Optional 11 4 Setup and operation 12 4 1 Preparations 12 4 2 Testing Single and Dual...

Page 5: ...BN034794AE ZP BN01E MTO106 5...

Page 6: ...program To help locate the presence of defects in transformers such as increased contact resistance in terminal connections and tap changers The instrument can also be used for general resistance mea...

Page 7: ...lowing shipment Our liability is specifically limited to replacing or repairing at our option defective equipment This warranty does not include batteries lamps or other expendable items where the ori...

Page 8: ...ground pin Do not defeat the safety ground in any manner The equipment must be connected to a grounded mains outlet 3 Ground lead The first connection made and last removed is the connection of instr...

Page 9: ...that are not intended for use together with the instrument Maintenance 1 DISCONNECT the MAINS plug before any cleaning or maintenance 2 Refer all servicing to Megger authorized personnel Do not attem...

Page 10: ...display 5 DISCHARGE Built in discharge circuit safely discharges the test object when test is completed LED and audio sig nal indicate the charging status 6 100 240V 5A 50 60Hz Mains input and fuse bo...

Page 11: ...proach 100 only very slowly Note If dual channel measurement is selected the above values are duplicated 3 3 Accessories Included Test lead black with banana connector and Kelvin clamp 10m 33ft 1 GC 3...

Page 12: ...current switch is set to OFF 2 Connect the Kelvin type test leads to the MTO106 see figures below The leads marked Generator to the CUR RENT OUTPUT terminals of corresponding colour and the leads mark...

Page 13: ...e indication of discharging 4 3 Testing Delta winding resistance Testing Delta winding resistance may be a very time consuming procedure in particular LV winding deltas The correct balance time can ta...

Page 14: ...with only small deviations between different tap position changes Fig 1 shows a typical behavior for a transformer tap changer in as new condition Fig 5 1 Winding resistance vs tap position for a new...

Page 15: ...cording to the method below 1 Run a normal winding resistance test accord ing to the instructions in section 4 2 Testing Single and Dual windings on page 12 2 Swap the terminals preferably by swapping...

Page 16: ...leads switched 3 Sense leads not connected 4 Current leads shorted 1 Increase test current 2 Check sense leads 3 Check sense leads 4 Check current leads U 0 06 mV 0 0 A No current loop current leads n...

Page 17: ...BN034794AE ZP BN01E MTO106 17 7 Specifications...

Page 18: ...mensions W x D x H 360 x 304 x 194 mm 14 2 x12 x 7 6 Weight 7 3 kg 16 lbs excl cables Display 4 inch backlit monochrome alphanumerical display Test leads 2 x 10 m 33 ft with banana connectors and Kelv...

Page 19: ......

Page 20: ...Equipment Fiber Optic Test Equipment Ground Resistance Test Equipment Insulation Power Factor C DF Test Equipment Insulation Resistance Test Equipment Line Testing Equipment Low Resistance Ohmmeters...

Reviews: