6. 

Testing a Charging Point

The PE Pre-Test is an integral safety 
feature of the EVCA210 adaptor. It 
allows the operator to test the PE 
conductor for possible presence of a 
dangerous voltage, prior to testing the 
charge point.

Under normal conditions, the PE 
conductor is connected to earth and 
therefore no hazardous voltage should 
be present. Should a fault condition 
occur e.g. if the PE conductor is 
connected to a phase or any insulation 
within the EVCA210 or associated plugs 
and cables has been damaged, then a 
hazardous situation may arise.

With the EVCA210 adaptor connected 
to the charging point, touch the PE 
Pre-test button with a bare finger. If the 
LED indicator illuminates, then there is 
a dangerous voltage present on the PE 
conductor. Stop testing immediately and 
investigate the circuit and rectify before 
continuing. Do not touch any metal 
parts while performing this test.

Possible faults are:

Voltage present on PE (e.g. connected 
to phase)

PE Missing or disconnected 

If the operator is isolated from ground through rubber matting or wearing gloves etc. the touch-
test result will be unreliable and an alternative method should be employed to confirm the PE 
connection.

7. 

Electrical Testing

The EVCA210 gives the operator the ability to connect their electrical test equipment to the 
charging point under test, in a controlled and safe manner, and to undertake the electrical safety 
testing of the charge point and its associated circuits. With the correct cable connected and the 
EVCA210 CP and PP settings correctly set (see below for details), the operator can connect either 
single or multifunction test equipment to the adaptor to undertake the following live tests:

Earth loop impedance 
RCD operation 
Phase sequence  
Proximity Pilot - PP State 

www.megger.com

EVCA210 

10

Testing a Charging Point

Summary of Contents for EVCA210

Page 1: ...EVCA210 Electric vehicle charge point adaptor User guide EN...

Page 2: ...pecification of its products from time to time without notice Although every effort is made to ensure the accuracy of the information contained within this document it is not warranted or represented...

Page 3: ...ted described in this user guide is in compliance with Directives 2014 30 EU and 2014 35 EU where they apply The full text of Megger Instruments EU declarations of conformity are available at the foll...

Page 4: ...Limited reserves the right to change the specification of these instruments at any time without notice Megger reserves the right to improve the content of this User Guide from time to time without no...

Page 5: ...ugs should not be used if any part is damaged All test leads supplied with the instrument form part of the measuring circuit of the instrument They must not be modified or changed in any way or be use...

Page 6: ...vant EU Directives Do not dispose of in the normal waste stream g Earth ground 3 General Description Type 1 Plug Type 2 Plug Case contents 1 x EVCA210 Electric Vehicle Charge point Adaptor 1 x 32 A Ty...

Page 7: ...PE terminal prior to undertaking any testing via a touch button electrode with LED lamp indication Live phase neutral indication of all three phases via LED lamps Rotary switch providing PP State Pro...

Page 8: ...instruments such as appropriate Megger MFT Multifunction testers With this adaptor charging points can be tested in accordance with IEC EN 61851 1 and IEC HD 60364 7 722 Before carrying out testing w...

Page 9: ...r fixed cable with Type 2 vehicle socket connector Type 1 connector plug for charging points with fixed cable and Type 1 vehicle socket connector Example Mitsubishi PHEV Note Only the EVCA210 UK is su...

Page 10: ...rectify before continuing Do not touch any metal parts while performing this test Possible faults are Voltage present on PE e g connected to phase PE Missing or disconnected If the operator is isolat...

Page 11: ...rent simulated vehicle states Selection of Vehicle State Vehicle State A Electric vehicle not connected B Electric vehicle connected not ready to charge C Electric vehicle connected ready to charge ve...

Page 12: ...d for measuring purposes only It is connected to the L1 N and PE terminals of the charge point so appropriate test instruments may be connected to the mains plug socket for testing In addition this so...

Page 13: ...as detailed in this user manual no special maintenance is required However if functional errors occur during normal operation contact your local Megger Repair Centre for assistance 16 Fuse Replacemen...

Page 14: ...V AC CAT II 250 V max 10 A Note Do not load mains socket simultaneously with measuring ports CP Signal output Ports Approx 12 V CAT 0 under normal condition Measurement category CAT II 250 V Altitude...

Page 15: ...rranty 3 years This product is warranted to the original purchaser against defects in material and workmanship for three years from the date of purchase During this warranty the manufacturer will eith...

Page 16: ...22 Application Photos www megger com EVCA210 16 Application Photos...

Page 17: ...23 Notes www megger com EVCA210 17 Notes...

Page 18: ...www megger com EVCA210 18 Notes...

Page 19: ...www megger com EVCA210 19 Notes...

Page 20: ...eet Dallas 75211 3422 T 1 214 333 3201 F 1 214 331 7399 USsales megger com Megger AB Rinkebyv gen 19 Box 724 SE 182 17 DANDERYD T 08 510 195 00 E seinfo megger com Megger Baker 4812 McMurry Avenue 805...

Reviews: