4. Parameter Setting (Main PCB)
4.1 Functions set by switch
Function setting-
SW4
1
2
Function
3
Function
OFF OFF
Without Compressor
emergency(Default)
OFF
Without Modular
emergency(Default)
OFF
ON
1# Compressor
emergency
ON
Modular emergency
ON
OFF
2# Compressor
emergency
ON
ON
/
Function setting-
SW5
1
2
Function
OFF
OFF
Without quiet mode(Default)
OFF
ON
Quiet
in night
ON
OFF
Quiet mode
ON
ON
Strong mode
3
4
Function
5
6
Function
7
8
OFF
OFF
First-ON (Default)
OFF
OFF
static pressure
0 Pa(Default)
Reserve
OFF
ON
Heating priority
OFF
ON
20 Pa
ON
OFF
Cooling priority
ON
OFF
50 Pa
ON
ON
Majority rule
ON
ON
80 Pa
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...