XE
Ground wire
5. Outdoor unit trouble shooting
5.1 E3 E4 Error Code
E3 / E4 : Discharge temperature
"Tda" "Tdb"
too high
Compressor discharge temperature sensor detected
Td ≥120
℃
and Lasts for
10s
,
whole system will stop running, after 4 minutes later will restart, but if stop running more
than
3 times within an hour
, ODU PCB will display E3 or E4 error code. Stop running
until power up again.
↓
Check whether Lack of refrigerant
1. No additional refrigerant?
2. Low pressure is too low?
3. High temperature of IDU air outlet?
Yes
→
Add refrigerant
NO
↓
Check whether Lack of frozen oil
Through monitoring software to check is the
system frequent to run the oil return mode
Yes
→
Add oil
NO
↓
Check whether high pressure too high
1. ODU fan running abnormal?
2. Condenser is dirty block?
Yes
→
1. Replace fan or fan motor
2. Clean the condenser
NO
↓
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...