1. IDU Error code table (No.16)
1.1 Temperature sensor failure (4)
Code
Definition
Possible reason for error code
A1
Indoor ambient temperature
1. Indoor unit
’s PCB failure
2. The fuse of indoor PCB is broken
3. Temperature sensor failure , or
exceed test limit
A2
Evaporator mid temperature sensor
A3
Evaporator inlet temperature sensor
A4
Evaporator outlet temperature sensor
1.2 Communication failure (2)
Code
Definition
Possible reason for error code
A9
The communication between indoor unit
and outdoor unit failed
1. The communication wire between
indoor unit and outdoor unit is
broken.
2. Indoor unit power failure
3. Indoor PCB failure
AA
The communication between indoor unit
and wire controller failed
1. The communication wire between
indoor unit and outdoor unit is
broken.
2. Indoor unit power failure
3. Indoor PCB failure
4. Wire controller is broken
Summary of Contents for ARV Series
Page 71: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 71...
Page 88: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 88...
Page 114: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 114...
Page 118: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 118...
Page 131: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 131...
Page 150: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 150 Symbol Description...
Page 151: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ 151...
Page 172: ...MegaLife ARV OUTDOOR UNIT ARV 6 ALL DC INVERTER T1 50 60HZ Service Manual 172...