background image

 

 

2. Installation and setup 

NOTE: 

Before installation, please inspect the unit. Be sure that nothing inside the package is 

damaged. Please keep the original package in a safe place for future use. 

 

2-1. Rear panel view 
Tower Unit 

 

 

 

 

1K (L)

 

2K (L)

 

3K(L) 

 

 
1.

 

AC input 

2.

 

Input circuit breaker 

3.

 

USB communication port 

4.

 

RS-232 communication port 

5.

 

SNMP intelligent slot 

6.

 

External battery connection 

7.

 

Output receptacles 

8.

 

Output circuit breaker 

9.

 

Output terminal 

 

2-2. Setup the UPS 

Step 1: UPS input connection 

Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension 
cords. The power cord is supplied in the UPS package.

   

 

 

Step 2: UPS output connection 

 

For socket-type outputs, simply connect devices to the outlets.   

 

For terminal-type input or outputs, please follow below steps for the wiring configuration: 

a) Remove the small cover of the terminal block 

b) Suggest using AWG14 or 2.1mm

2

 power cords.   

c) Upon completion of the wiring configuration, please check whether the wires are 

securely affixed. 

d) Put the small cover back to the rear panel. 

 

Summary of Contents for ME-1000-WTU

Page 1: ...USER MANUAL ME 1000 WTU ME 2000 WTU ME 3000 WTU Online UPS Uninterruptible Power Supply System...

Page 2: ...2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 3 3 Operations 5 3 1 Button operation 5 3 2 LCD Panel 5 3 3 Audible Alarm 7 3 4 LCD display wordings index 7 3 5 UPS Setting 7 3 6...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...ker 9 Output terminal 2 2 Setup the UPS Step 1 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords The power cord is supplied in the UPS p...

Page 6: ...seconds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 5 Install so...

Page 7: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Sele...

Page 8: ...frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS...

Page 9: ...Charger FU Bypass frequency unstable EE EEPROM error 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and paramet...

Page 10: ...ency is 60Hz 04 ECO enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose the following two options ENA ECO mode enable DIS ECO mode disable Default 05 ECO voltage...

Page 11: ...Vac Default 264Vac LLS Bypass low voltage point 170 220 setting the low voltage point in parameter 3 from 170Vac to 220Vac Default 170Vac 8 Autonomy limitation setting Interface Setting Parameter 3 Se...

Page 12: ...When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range...

Page 13: ...attery is not connected Sounding every second Over Charge Sounding every second Over temperature Sounding every second Charger failure Sounding every second Battery fault Sounding every second Out of...

Page 14: ...e every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS...

Page 15: ...ity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 05 on LCD display At the same time alarm is continuously soundi...

Page 16: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Page 17: ...linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 87 90 Battery Mode 83 87 89 BATTERY Standard Model Battery Type...

Reviews: