ME225

PowerTorq Series

Pneumatic Actuator Instruction Manual

WARNING

Failure to follow these instructions or to 

properly install and maintain this 

equipment could result in an explosion 

and/or  fire  causing  property  damage  and 

personal injury or death.

Install, operate and maintain Marshall 

Excelsior Co. equipment in accordance 

with federal, state, and local codes and these 

instructions.  The installation in most states 

must also comply with NFPA Pamphlet #58, 

ANSI K61.1 and DOT standards.

Proper installation of remote actuation 

devices should include thermal protection 

to close the internal valve in case of a fire.  

This pneumatic actuator kit includes thermal 

protection.

Only personnel trained in the proper 

procedures, codes, standards, and regulations 

of the LP-Gas or anhydrous ammonia (NH3) 

industries should install and service this 

equipment.

INTRODUCTION

Scope of Manual

This manual covers instructions for the ME225 

Pneumatic Actuator kit.  This kit allows for remote 

operation of the ME990-10 (Fisher

®

 C407) internal valve.

DESCRIPTION

The ME225 Marshall Excelsior Co. Pneumatic 

Actuator kit fits the ME990-10 (Fisher

®

 C407) 1-1/4” 

NPT internal valve to allow for remote valve operation 

utilizing air  pressure.  Applying air pressure to the 

actuator moves the drive coupling and the internal 

valve shaft to open the valve.  Upon loss of air pressure, 

the valve’s operating lever immediately returns to the 

closed position.

Type ME225 – 

For ME990-10 (Fisher

®

  type  C407)      

internal valve (1-1/4” model)

This kit features a spring return design that eliminates 

the need for an air return.  

SPECIFICATIONS

Pressure Source: Air

Cylinder Pressure Limits:                Minimum – 20 psig

                                                     Maximum – 125 psig

                                         Recommended – 30-50 psig

Temperature Limits:  -60°F to 250°F

Return Mechanism: Spring only – no air

MAINTENANCE

A simple preventive maintenance program for the 

valve and its controls will eliminate many potential 

problems.  

Marshall Excelsior Co. recommends these steps be 

conducted at least once a month:

1.  Inspect the operating lever to see that it operates 

freely.

2. 

Confirm the actuator fully opens and closes the 

internal valve without sticking. Keep the actuator’s 

drive coupling free of any build-up of mud, 

corrosion, or other foreign material. Such a 

build-up could prevent the actuator from closing 

which could jam the internal valve in the open 

position.  Do not permit this condition to occur.

3.  Because the actuator has a sealed housing, 

internal lubrication is not required.  For smooth 

operation, lubricate the operating coupling joint.

4.  Inspect, clean and oil all operating controls.

Marshall Excelsior Co.

1506 George Brown Drive Marshall, MI  49068

Phone (269) 789-6700  Fax (269) 781-8340

The contents of this publication are for informational purposes only.  While every effort has been made to ensure accuracy, these contents are not to be construed as warranties or guarantees, expressed or implied, regarding the products or services described herein or 

for their use or applicability.  Marshall Excelsior Co. reserves the right to modify or improve the designs or specifications of such products at any time without notice.  The MECTM logo is the trademark of Marshall Excelsior Co.  Fisher® and Fisher® Internal Valves are 

the trademarks of Emerson Electric Co.

Instruction #461 Rev B  1/12