DC20D MK2 GENSET CONTROLLER USER MANUAL
23
C
Over current
alarm
1-2000A
(500A)
When the current is higher than the
value and comes into over current
delay but still higher (over current
delay), then over current alarms. If the
value is set as 2000, then the alarm is
disabled.
D
Over phase
current delay
0-3600.0s
(1296s)
When this parameter is set to 0, the
over current delay is the inverse time;
if not, the over current delay is the time
set for this parameter.
E
485 baud rate 0-4800
1-9600
2-19200
3-38400
4-57600
5-115200
RS485 communication baud rate
selection.
F
485
CRC
setting
0-CRC L_H
1-CRC H_L
Sequence selection of RS485
communication protocol CRC;
12. Alarm code
Code
Meaning
Code
Meaning
ALA.01
Emergency stop alarm
ALA.13
Pressure sensor disconnected
alarm
ALA.02
Over speed alarm
ALA.14
Coolant temperature sensor
disconnected alarm
ALA.03
Under speed alarm
ALA.15
Over frequency alarm
ALA.04
Low oil pressure alarm-sensor
ALA.16
Under frequency alarm
ALA.05
Low oil pressure alarm-switch
ALA.17
Over voltage alarm
ALA.06
High coolant temperature
alarm-sensor
ALA.18
Under voltage alarm
ALA.07
High coolant Temperature
alarm-switch
ALA.19
Over current alarm
ALA.08
High oil temperature alarm-
switch
ALA.20
Start failure alarm
ALA.09
Low fuel level warning-switch
ALA.21
Stop failure alarm-RPM
ALA.10
Low coolant level alarm-switch ALA.22
Stop failure alarm-Frequency
ALA.11
Speed lost alarm
ALA.23
Stop failure alarm-Oil pressure
sensor
ALA.12
Low battery voltage warning
ALA.24
Stop failure alarm-Oil pressure
switch
13. Fault finding
Symptoms
Possible Solutions
Controller no response
with power
Check DC voltage.
Check DC fuse.
Check if the terminal 1 and 2 is with battery voltage.
Genset shutdown
Check the water temperature is too high or not.