This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS DC DIN

rail mounted DC power & energy meter with RS-485 or TCP communications. These instructions are given using

the Windows OS.

1. Supplied Items

Check that the meter and equipment matches your order specifications and has not been damaged during shipping. The following

component(s) are included in the package:

Quick Start Guide (

DTS DC Application / Connection Examples

in section 2)

DTS DC power monitor. Check input ranges, output configuration and auxiliary power supply (if applicable) on the label of the unit. For

a more detailed explanation of the part number please download the latest version of the DTS DC datasheet from

http://www.measurlogic.com/MonitorsMeters/DCsolarPV/dts-dc.html

2. Connecting the DTS DC

Wiring Voltage and Current Inputs

The DTS DC is connected as a 3 wire configuration reducing the possibility of in-correct connections resulting in damage to the instrument. It

accepts a DC voltage input directly up to 800Vdc (model dependant). The current can be from a 50-100mV shunt or up to 10A direct

connection (model dependant).

If there are any questions please call Measurlogic before powering up the unit

. Please refer to

Application/Connection Examples

for information on wiring conventions.

Input wiring terminals are clearly indicated and located on the upper side of the DTS DC label. The Current and Voltage terminal strip is

pluggable to allow easy replacement of the DTS DC, if required. Removing the terminal strip should only be done once power has been

removed from the DTS DC. Input wiring terminals accept 2.5 mm

2

(12 awg) wire. The wires are connected by means of screw terminals that

clamp down onto the input wires. The voltage input requires fusing, not included, (see diagrams below) and should be rated at ≤ 1A. Please

check with local code requirements to ensure correct installation.

Wiring Auxiliary Power Input (AUX)

The DTS DC meter is powered from a DC auxiliary supply in the following ranges. (Fuses not included with meter but are offered as an

option). See the rating label of the unit for more information.

12 Vdc

OR

24 Vdc

OR

48 Vdc

Auxiliary power will not be needed for “self-powered” models

Note:

It is important to pay attention to the polarity when using a DC power supply.  See label above for a reference to the polarity.

Incorrect connection

will

damage the DTS DC.

The following connection diagrams depict some examples of typical applications.

If there are any variances please consult Measurlogic

Application/Connection Examples

SHUNT – Current Measurement in -VE Leg

(recommended)

5A Direct – Current Measurement in -VE Leg

HALL EFFECT – Current Measurement in

+VE

Leg

DC Aux

Not required for

“self-powered”

models

DC Aux

Not required for

“self-powered”

models

Source

Load

+

-

+

-

Current Dir. Arrow on CT

DC Aux

Not required for

“self-powered”

models

Source

Load

5A Max

+

-

Source

Load

Shunt

+

-

Twist shunt

output

conductors

(1 twist per inch)