TDR DIN rail with Three Phase or High Input Range

 

TDR-240-24    INPUT: 380 -480VAC   0.69A 50/60Hz   OUTPUT: 24V  10A 
TDR-240-48    INPUT: 380 -480VAC   0.69A 50/60Hz   OUTPUT: 48V   5A 
TDR-480-24    INPUT: 380 -500VAC      1A 50/60Hz   OUTPUT: 24V  20A 
TDR-480-48    INPUT: 380 -500VAC      1A 50/60Hz   OUTPUT: 48V  10A 
TDR-960-24    INPUT: 380 -500VAC      2A 50/60Hz   OUTPUT: 24V  40A 
TDR-960-48    INPUT: 380 -500VAC      2A 50/60Hz   OUTPUT: 48V  20A 

 

 

Introduction 

TDR series is the next generation of Mean Well DIN rail power supplies with three-phase or high input range, this 
three-phase DIN unit not only has a slim design of 110mm in width but also possesses a high efficiency of up to 
94.5%. Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit 

in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a 
heat source. 

2

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on 

the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not 
allowed. 

 
 
 
 
 
 

3

Use copper wire only, and recommended wires are shown as below. 

AWG 

18 16 14 12 10 

Rated Current of 
Equipment (Amp) 

6A 

6-10A  13-16A 16-25A 25-32A 

Cross-section of 
Lead(mm

2

 ) 

0.75 1.00  1.5  2.5  4 

Note: Current each wire carries should be de-rated to 80% of the current suggested 

  above when using 5 or more wires connected to the unit. 

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are 
securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make 
sure each contact is connected to wires to prevent too much current stress on a single contact.   

4

Use wires that can withstand temperatures of at least 80°C for TDR-480/960, 85°C for TDR-240. 

5

Recommended wire strapping length is 5mm (0.197”). 

6

Recommended screwdriver is

 

4mm, slotted type. 

7

The recommended torque setting for terminals is shown as below. 

Model I/P  O/P 

TDR-240 

10 kgf-cm (9 Lb-in) 

10 kgf-cm (7 Lb-in) 

TDR-480 

10 kgf-cm (9 Lb-in) 

10 kgf-cm (9 Lb-in) 

TDR-960 

10 kgf-cm (9 Lb-in) 

8 kgf-cm (7 Lb-in) 

 